EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 11. Excel 10 W7750 Controller Ordering Information. (Continued)

 

 

 

Part Number

Product Description

Comments

 

 

 

ML6464A1009

Direct Coupled Actuator, 66 lb-in. torque,

 

Series 60

 

 

 

 

ML6474A1008

Direct Coupled Actuator, 132 lb-in. torque,

 

Series 60

 

 

 

 

ML6185A1000

Direct Coupled Actuator, 50 lb-in. spring return

Series 60

 

 

 

V5852A/V5862A

Two-way terminal unit water valve; 0.19, 0.29,

Use with M6410 Valve Actuator. Close-off rating

 

0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm)

for 0.19 to 1.9 Cv is 65 psi; for 2.9 and 4.9, Cv is

 

or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

45 psi. (Coefficient of volume or capacity index

 

 

Cv = gallons per minute divided by the square

 

 

root of the pressure drop across the valve.)

 

 

 

V5853A/V5863A

Three-way mixing terminal unit hot water valve;

Use with M6410 Valve Actuator. Close-off rating

 

0.19, 0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in.

for 0.19 to 0.74 Cv is 55 psi; 1.2 and 1.9 Cv is 22

 

npt (13 mm) or 2.9 and 4.9 Cv 3/4 in. npt (19

psi; 2.9 and 4.9 Cv is 26 psi.

 

mm)

 

 

 

 

R8242A

Contactor, 24 Vac coil, DPDT

 

 

 

AT72D, AT88A, AK3310, etc.

Transformers

 

 

 

EN 50 022

DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.)

Obtain locally: Each controller requires 5 in.

 

 

 

Two DIN rail adapters

Obtain locally: Part number TKAD, from Thomas

 

 

and Betts, two for each controller.

 

 

 

 

Cabling:

 

 

 

 

Serial Interface Cable, male DB-9 to female

Obtain locally from any computer hardware

 

DB-9 or female DB-25.

vendor.

 

 

 

Honeywell

LONWORKS Bus (plenum): 22 AWG (0.34 mm2)

Level IV 140°F (60°C) rating

AK3791 (one twisted pair)

twisted pair solid conductor, nonshielded or

 

AK3792 (two twisted pairs)

Echelon approved cable.

 

 

 

 

Honeywell AK3781 (one

LONWORKS Bus (nonplenum): 22 AWG (0.34

Level IV 140°F (60°C) rating

twisted pair) AK3782 (two

mm2) twisted pair solid conductor, nonshielded

 

twisted pairs)

or Echelon approved cable.

 

 

 

 

Honeywell AK3725

Inputs: 18 AWG (1.0 mm2) five wire cable

Standard thermostat wire

 

bundle

 

 

 

 

Honeywell AK3752 (typical or

Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2)

NEC Class 2 140°F (60°C) rating

equivalent)

 

 

 

 

 

Honeywell AK3702 (typical or

18 AWG (1.0 mm2) twisted pair

Non-plenum

equivalent)

 

 

 

 

 

Honeywell AK3712 (typical or

16 AWG (1.3 mm2) twisted pair

Non-plenum

equivalent)

 

 

 

 

 

Honeywell AK3754 (typical or

14 AWG (2.0 mm2) two conductor

Non-plenum

equivalent)

 

 

 

 

 

Step 6. Configure Controllers

Excel E-Vision PC Software is used to configure W7750 Controllers to match their intended application. The E-Vision User Guide, form number 74-2588 provides details for operating the PC software.

W7750 Controllers are shipped from the factory with a default hardware configuration. On power-up, the controller configuration parameters are set to the default values listed in Table 20 in Appendix C. The controller can operate normally in this mode (if the equipment and wiring match the default setup), and given valid sensor inputs, the outputs are controlled appropriately to maintain space temperature at the default setpoint. The default I/O arrangement for the W7750A

is printed on the terminal labels. Also see the wiring details in Fig. 27 in Step 4, Prepare Wiring Diagrams. The labeled I/O terminals are defined in Table 10.

Step 7. Troubleshooting

Troubleshooting Excel 10 Controllers and Wall Modules

In addition to the following information, refer to the Installation Instructions and Checkout and Test manual for each product. Most products have a Checkout and Test section in their Installation Instructions manual. If not, look for a separate Checkout and Test manual. See the Applicable Literature section for form numbers.

74-2958— 1

48

Page 48
Image 48
Honeywell W7750A specifications Configure Controllers, Troubleshooting Excel 10 Controllers and Wall Modules, Cabling