Honeywell W7750A specifications Last NET, Offset Absolutemiddle, None Normal, Bypassonly

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 97
Image 97

 

 

 

 

 

 

 

Table 25. Configuration Parameters. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

 

E-Vision

 

 

Direct

Hardware

Manual

 

NOTE: Physical I/O points that are configurable are in Table 20.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

User Address

 

NvName

 

Field Name

(Metric) or States plus Range

ofState

Stateor

 

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

OvrdPriority

nciConfig

OverridePriority

LAST

0

 

NET

P

 

X

X

 

 

 

OverridePriority configures the override arbitration between ManOcc,

 

 

 

 

 

 

NET

1

 

 

 

 

 

 

 

 

 

 

Bypass.state, and the wall module override button. If OverridePriority is 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(LAST), then the last command received from either the wall module or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

iManOcc determines the effective override state. If OverridePriority is 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(NET), this specifies that when ManOcc is not OC_NUL, that the effective

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

occupancy is ManOcc regardless of the wall module override state.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UseWallModStpt

nciConfig

UseWallModStPt

FALSE

0

 

TRUE

P

 

X

X

 

 

 

UseWallModStpt specifies the OC_OCCUPIED temperature setpoint

 

 

 

 

 

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

source. If UseWallModStpt is 0 (FALSE), then the occupied TempSetPts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are used when the effective occupancy is OC_OCCUPIED. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UseWallModStpt is 1 (TRUE), then the wall modules setpoint knob is used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when the effective occupancy is OC_OCCUPIED. SetPt overrides all.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SetPtKnob

nciConfig

SetPntKnob

OFFSET

0

 

ABSOLUTE_MIDDLE

P

 

X

X

 

 

 

SetPntKnob specifies the usage of the setpoint knob when

 

 

 

 

 

 

ABSOLUTE_MIDDLE

1

 

 

 

 

 

 

 

 

 

 

UseWallModStPt is TRUE. When SetPntKnob is 0 (ABSOLUTE_MIDDLE),

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the setpoint knob directly determines the center point of between the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_OCCUPIED cooling and heating setpoints. When SetPntKnob is 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(OFFSET), the effective setpoint is calculated by adding the remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setpoint potentiometer value (center scale = 0) to the appropriate value of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TempSetPts.

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OvrdType

nciConfig

OverrideType

NONE

0

 

NORMAL

P

 

X

X

 

 

 

OverrideType specifies the behavior of the override button. If the

 

 

 

 

 

 

NORMAL

1

 

 

 

 

 

 

 

 

 

 

OverrideType is 0 (NONE) then the override button is disabled. An

 

 

 

 

 

 

BYPASS_ONLY

2

 

 

 

 

 

 

 

 

 

 

OverrideType of 1 (NORMAL), causes the override button to set the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OverRide state to OC_BYPASS for Aux2SetPt.BypassTime seconds when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the override button has been pressed for approximately 1 to 4 seconds, or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to set the OverRide state to UNOCC when the button has been pressed for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

approximately 4 to 7 seconds. When the button is pressed longer than

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

approximately 7 seconds, then the OverRide state is set to OC_NUL. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OverrideType is 2 (BYPASS_ONLY), the override button sets the OverRide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

state to OC_BYPASS for Aux2SetPt.BypassTime seconds on the first

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

press. On the next press, the OverRide state is set to OC_NUL.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 26. LONMARK® /Open System Points.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ValueofState

DigitalStateor

 

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

User Address

 

NvName

 

Field Name

 

(Metric) or States plus Range

 

 

Default

 

 

 

 

 

 

 

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciNodeSendT

 

 

 

Seconds

 

 

 

0

 

 

 

 

 

 

 

The maximum time between updates of network variable outputs from the

 

 

 

(SNVT_time_sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

node object.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciRtuSendT

 

 

 

Seconds

 

 

 

0

 

 

 

 

 

 

 

The SGPUC and SGPU time (heart beat time) between updates of network

 

 

 

(SNVT_time_sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

variable outputs.NOTE: RtuSendT should be set to 55 seconds by a

74-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

management node to be compatible with a Honeywell system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciRtuRcvT

 

 

 

Seconds

 

 

 

0

 

 

 

 

 

 

 

This is the failure detection time for network SGPUC and SGPU variables

2958

 

 

(SNVT_time_sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outputs.NOTE: RtuRcvT should be set to 300 seconds by a management

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

node to be compatible with a Honeywell system.

— 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 97
Image 97