EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 5. Modes Of Operation For The Excel 10 W7750 Controller (Continued).

 

 

 

Mode

Description

Events causing a controller to switch to this mode

 

 

 

UNOCCUPIED

Controller occupancy mode was

Network input (DestManOcc) containing a time-of-day schedule

 

overridden to Unoccupied mode

override signal of UNOCCUPIED from the Excel 10 Zone Manager or

 

 

other LONWORKS Bus device.

 

 

 

BYPASS

Controller occupancy mode was

DI (Bypass) was pressed, and the Bypass duration timer has not yet

 

overridden to Bypass the current

expired, or the network input DestManOcc has a value of BYPASS.

 

Unoccupied mode

 

 

 

 

NOT

No Bypass action

No Override input received.

ASSIGNED

 

 

 

 

 

Operational Modes (User Address: StatusMode)

 

 

 

 

START-UP

On power-up, provides a staggered

This mode occurs on controller power-up, and after downloading to the

AND WAIT

start sequence to evenly apply the load

controller from the configuration tool. Temperature control loops are

 

to the electrical system.

disabled.

 

 

 

COOLING

The Excel 10 is controlling the Cooling

Space temperature has risen above the current cooling setpoint, or the

 

mode.

network input (DestHvacMode) is COOL.

 

 

 

HEATING

The Excel 10 is controlling the Heating

Space temperature has fallen below the current heating setpoint, or the

 

mode.

network input (DestHvacMode) is HEAT.

 

 

 

EMERGENCY

Compressors are disabled and only

The network input (DestManHvacMode) is EMERG_HEAT.

HEAT

Auxiliary Heat stages are allowed to

 

 

operate.

 

 

 

 

OFF MODE

The heat/cool control is turned off

Network input (DestManMode) containing AHU operational mode

 

immediately. The node is not running its

information from C-Bus has value of MORNING WARM-UP.

 

normal temperature control.

 

 

 

 

DISABLED

The heat/cool control and frost

MODE

protection are turned off immediately.

 

 

The node is not running its normal

 

 

temperature control.

 

 

 

 

SMOKE

The node has entered a smoke

Network input (DestEmergCmd) containing smoke control signal from

EMERGENCY

emergency. The fan and dampers are

another LONWORKS Bus device has value of SMOKE_EMERG.

 

then set to the conditions configured by

 

 

SmkCtlMode. The control remains in

 

 

SMOKE_ EMERGENCY until power is

 

 

cycled or the node receives

 

 

DestEmergCmd set to

 

 

EMERG_NORMAL.

 

 

 

 

FREEZE

The temperature control is set to HEAT

The Window digital input detects an open window.

PROTECT

with the setpoint set to the frost limit

 

 

setpoint 46.4°F (8°C).

 

 

 

 

MANUAL

The physical outputs are being

Typically this is done by the user through E-Vision or XBS by setting

POSITION

controlled manually. The temperature

the point DestManMode to MANUAL mode.

 

control loop is turned off.

 

 

 

 

FAN ONLY

Control algorithm is disabled, except

The space temperature sensor has failed, or the network input

 

that the fan is turned on.

(DestHvacMode) is FAN ONLY.

 

 

 

DISABLED

Control algorithm is shut off.

Network input (DestManMode) containing AHU operational mode

 

 

information from an operator or the network that has a value of

 

 

DISABLED.

 

 

 

NOTE: During all modes all digital and analog physical inputs are periodically read, the diagnostic output network variables can be polled, the input network variables are received, and the output network variables are sent periodically.