Honeywell W7750A specifications Configuration Parameters

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 94
Image 94

74-2958— 1

94

Table 25. Configuration Parameters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

Test

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Physical I/O points that are configurable are in Table 20.

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciDeviceName

 

 

 

ASCII Blanks

 

 

 

 

 

 

 

DeviceName is an 18 character field used to identify the node uniquely as

 

 

 

 

 

 

 

 

 

 

 

 

 

one object at the site or project. The contents of the DeviceName is

 

 

 

 

 

 

 

 

 

 

 

 

 

maintained by a management node. If DeviceName is all ASCII blanks, it is

 

 

 

 

 

 

 

 

 

 

 

 

 

considered unconfigured.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciApplVer

application_type

0 to 255

 

0

 

 

 

 

 

 

 

ApplicationType identifies the current application number of the Excel 10.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciApplVer

version_no

0 to 255

 

0

 

 

 

 

 

 

 

VersionNumber identifies the version number of the Excel 10 application.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciApplVer

time

Seconds

 

0

 

 

 

 

 

 

 

The time stamp of the last change to the Excel 10 application

 

 

 

 

 

 

 

 

 

 

 

 

 

configuration. Time meets the ANSI C time stamp requirement specifying

 

 

 

 

 

 

 

 

 

 

 

 

 

the number of seconds elapsed since midnight (0:00:00), January 1, 1970.

 

 

 

 

 

 

 

 

 

 

 

 

 

It is represented in the Intel Format.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FanMode

nciConfig

FanMode

AUTO_FAN

0

AUTO_FAN

P

 

X

X

 

 

 

FanMode specifies the operation of the fan. If the FanMode is 0

 

 

 

CONTINUOUS_FAN

1

 

 

 

 

 

 

 

 

(AUTO_FAN), then the fan cycles on and off with demand for cooling and

 

 

 

 

 

 

 

 

 

 

 

 

 

may cycle with heating if FanOnHeat is TRUE. If the FanMode is 1

 

 

 

 

 

 

 

 

 

 

 

 

 

(CONTINUOUS_FAN), then the fan runs continuously when the effective

 

 

 

 

 

 

 

 

 

 

 

 

 

occupancy is OC_OCCUPIED or OC_BYPASS. The fan cycles on and off

 

 

 

 

 

 

 

 

 

 

 

 

 

with demand for cooling and may cycle with heating if FanOnHeat is TRUE

 

 

 

 

 

 

 

 

 

 

 

 

 

during the OC_UNOCCUPIED or OC_STANDBY modes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EconMode

nciConfig

EconEnable

DIGITAL_IN

0

ECON_NUL

P

 

X

X

 

 

 

EconEnable specifies the method used to determine when outside air is

 

 

 

OD_TEMP

1

 

 

 

 

 

 

 

 

suitable for use to augment cooling. The valid values are according to the

 

 

 

OD_ENTH_A_TYPE

2

 

 

 

 

 

 

 

 

enumerated list that is shown in the Engineering Units/States column.

 

 

 

OD_ENTH_B_TYPE

3

 

 

 

 

 

 

 

 

 

 

 

 

OD_ENTH_C_TYPE

4

 

 

 

 

 

 

 

 

 

 

 

 

OD_ENTH_D_TYPE

5

 

 

 

 

 

 

 

 

 

 

 

 

DIFF_TEMP

6

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE_ENTH

7

 

 

 

 

 

 

 

 

 

 

 

 

DIFF_ENTH

8

 

 

 

 

 

 

 

 

 

 

 

 

ECON_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SmkCtlMode

nciConfig

SmokeControl

FAN_OFF_DAMPER_CLOSED

0

FAN_OFF_DAMPER_

P

 

X

X

 

 

 

SmokeControl specifies the operation of the economizer damper and the

 

 

 

FAN_ON_DAMPER_OPEN

1

CLOSED

 

 

 

 

 

 

 

fan when the mode is SMOKE_EMERGENCY.

 

 

 

FAN_ON_DAMPER_CLOSED

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HeatCycHr

nciConfig

ubHeatCph

2 to 12

 

6

P

 

X

X

 

 

 

HeatCph specifies the mid-load number of on/off cycles per hour when the

 

 

 

 

 

 

 

 

 

 

 

 

 

mode is HEAT. In addition the cycle rate specifies the minimum on and off

 

 

 

 

 

 

 

 

 

 

 

 

 

time. Refer to Table 17 Interstage Minimum Times of the System

 

 

 

 

 

 

 

 

 

 

 

 

 

Engineering Guide for the actual values.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CoolCycHr

nciConfig

ubCoolCph

2 to 12

 

3

P

 

X

X

 

 

 

CoolCph specifies the mid-load number of on/off cycles per hour when the

 

 

 

 

 

 

 

 

 

 

 

 

 

mode is COOL. In addition the cycle rate specifies the minimum on and off

 

 

 

 

 

 

 

 

 

 

 

 

 

time. Refer to Table 17 Interstage Minimum Times of the System

 

 

 

 

 

 

 

 

 

 

 

 

 

Engineering Guide for the actual values.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FanRunOnCool

nciConfig

ubFanRunonCoolS0

Seconds

 

0

P

 

X

X

 

 

 

FanRunonCool specifies how long the fan runs after all the cooling stages

 

 

 

0 to 120

 

 

 

 

 

 

 

 

 

have turned off. The fan is turned off FanRunonCool seconds after all the

 

 

 

 

 

 

 

 

 

 

 

 

 

cooling demand has turned off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FanRunOnHeat

nciConfig

ubFanRunonHeatS0

Seconds

 

0

P

 

X

X

 

 

 

FanRunonHeat specifies how long the fan runs after all the heating stages

 

 

 

0 to 120

 

 

 

 

 

 

 

 

 

have turned off. The fan is turned off FanRunonHeat seconds after all the

 

 

 

 

 

 

 

 

 

 

 

 

 

heating demand has turned off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 94