Table 20. Input/Output Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[0]

COOL_STAGE_1

1

 

NETWORK DO(FREE1)

 

 

 

 

X

 

 

DigitalOut[0] specifies which logical digital output function is assigned to the

 

 

 

 

COOL_STAGE_2

2

 

(Value of State is 25)

 

 

 

 

 

 

 

digital physical output according to the enumerated list that is shown in the

 

 

 

 

COOL_STAGE_3

3

 

 

 

 

 

 

 

 

 

Engineering Units/States column. The W7750 Controllers are configured at

 

 

 

 

COOL_STAGE_4

4

 

 

 

 

 

 

 

 

 

the factory with the enumerated value in the Default column. Only

 

 

 

 

HEAT_STAGE_1

5

 

 

 

 

 

 

 

 

 

DigitalOut[0] through DigitalOut[5] are available in the W7750A model

 

 

 

 

HEAT_STAGE_2

6

 

 

 

 

 

 

 

 

 

which can configure staged outputs. The W7750A Controller can drive

 

 

 

 

HEAT_STAGE_3

7

 

 

 

 

 

 

 

 

 

Series 60 Floating Control to modulate cooling valves, heating valves and

 

 

 

 

HEAT_STAGE_4

8

 

 

 

 

 

 

 

 

 

economizers. (No PWM outputs are allowed in the W7750A model.) The

 

 

 

 

CHANGE_OVER_RELAY

9

 

 

 

 

 

 

 

 

 

controller is configured at the factory with the enumerated value in the

 

 

 

 

FAN_OUT

10

 

 

 

 

 

 

 

 

 

Default column. The eight outputs on the W7750B are all digital outputs.

 

 

 

 

AUX_ECON

11

 

 

 

 

 

 

 

 

 

The eight outputs on the W7750C consist of five digital and three analog

 

 

 

 

OCCUPANCY_STATUS

12

 

 

 

 

 

 

 

 

 

outputs.

 

 

 

 

ECON_OPEN

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECON_CLOSE

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL_OPEN

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL_CLOSE

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_OPEN

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_CLOSE

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_COOL_STAGE_1

19

 

 

 

 

 

 

 

 

 

 

69

 

 

 

HEAT_COOL_STAGE_2

20

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_COOL_STAGE_3

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_COOL_STAGE_4

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FREE1

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FREE2

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FREE1_PULSE_ON

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FREE1_PULSE_OFF

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECON_PWM

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_PWM

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL_PWM

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNUSED

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[1]

See DigitalOut[0] enumerated

1-31

FAN_OUT

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

 

 

 

 

values

,255

(Value of State is 10)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[2]

See DigitalOut[0] enumerated

1-31

COOL_STAGE_2

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

 

 

 

 

values

,255

(Value of State is 2)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[3]

See DigitalOut[0] enumerated

1-31

HEAT_STAGE_1

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

 

 

 

 

values

,255

(Value of State is 1)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[4]

See DigitalOut[0] enumerated

1-31

HEAT_STAGE_2

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

 

 

 

 

values

,255

(Value of State is 3)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[5]

See DigitalOut[0] enumerated

1-31

HEAT_STAGE_1

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

 

 

 

 

values

,255

(Value of State is 5)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[6]

See DigitalOut[0] enumerated

1-31

UNUSED

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

 

 

 

 

values

,255

(Value of State is 255)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

DigitalOut[7]

See DigitalOut[0] enumerated

1-31

UNUSED

 

 

 

 

X

 

 

See DigitalOut[0] for enumerated names. The W7750 Controllers are

74-

 

 

 

values

,255

(Value of State is 255)

 

 

 

 

 

 

 

configured at the factory with the enumerated value in the Default column.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect

HtPump

CONV

0

 

CONV

P

 

 

X

 

 

 

HtPump specifies the type of equipment being controlled. When HtPump is

2958

 

 

 

HP

1

 

 

 

 

 

 

 

 

 

0 (CONV), the node is controlling conventional gas or electric heat. When

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HtPump is 1 (HP), the node is controlling a heat pump.

— 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 69
Image 69