Honeywell W7750A specifications Nema class 2 transformer voltage output limits

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 34
Image 34

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

 

27

 

26

 

25

VOLTAGE

24

23

 

 

22

SECONDARY

21

20

OUTPUT

DEVICE

POWER

TRANSFORMER

TRIAC LINES

TO ACTUATORS

 

 

 

 

 

 

 

 

 

 

AND CONTACTORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

18

17

16

15

14

050100150200

% OF LOAD

M993

 

Fig. 21. NEMA class 2 transformer voltage output limits.

Attach earth ground to W7750 Controller terminal 1. See Fig. 22, 23 and 24, 27 through 35.

CONNECT POWER TO TERMINALS 24 AND 25

W7750B,C

 

 

25 24

22

20

1

 

 

EARTH

M10089B

GROUND

 

Fig. 22. Power wiring details for one Excel 10 per

transformer.

See Fig. 23. for wiring more than one Excel 10 per transformer.

TRANSFORMER

120/240 VAC

24 VAC

 

W7750B,C

W7750B,C

W7750B,C

 

25 24

25 24

25 24

1

1

 

1

EARTH

EARTH

EARTH

M10090A

GROUND

GROUND

GROUND

 

Fig. 23. Power wiring details for two or more Excel 10s per transformer.

IMPORTANT

If the W7750 Controller is used on Heating and Cooling Equipment (UL 1995 U.S. only) devices and the transformer primary power is more than 150 volts, connect the transformer secondary to earth ground, see Fig. 24.

74-2958— 1

34

Page 34
Image 34
Honeywell W7750A Nema class 2 transformer voltage output limits, Power wiring details for one Excel 10 per Transformer