74-2958— 1

88

Table 23. Status Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

WSHPEnable

nvoData1

WSHPEnable

FALSE

0

 

FALSE

 

 

X

 

 

 

 

WSHPEnable: WSHPEnable reports the state of the current state of

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

nviWSHPEnable. The states for nviWSHPEnable are as follows: If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviWSHPEnable.state is SW_OFF and the nviWSHPEnable.value is 0,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then WSHPEnable is 0 (Disable Water Source Heat Pump). If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviWSHPEnable.state is SW_ON and the nviWSHPEnable.value is 0, then

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WSHPEnable is 0 (Disable Water Source Heat Pump). If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviWSHPEnable.state is SW_ON and the nviWSHPEnable.value is not 0,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then WSHPEnable is 1 (Enable Water Source Heat Pump). If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviWSHPEnable.state is SW_NUL and the nviWSHPEnable.value is any

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value, then WSHPEnable is 1 (Enable Water Source Heat Pump when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviWSHPEnable is not bound to another node).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoData2

FieldNo

UPDATE_ALL_FIELDS

 

 

UPDATE_ALL_FIELDS

 

 

 

 

 

 

 

nvoData2. FieldNo: nvoData2 and nvoCtlDataG2 are output network

 

(nvoCtlDataG2)

 

BYPASS_TIMER_FIELD

 

 

 

 

 

 

 

 

 

 

variables indicating the node status. The information contained in these

 

 

 

TEMP_CONTROL_PT_FIELD

 

 

 

 

 

 

 

 

 

 

network variables are typically used to display the node status on an

 

 

 

SPACE_TEMP_FIELD

 

 

 

 

 

 

 

 

 

 

operator terminal, used in a trend log, or used in a control process. The

 

 

 

DISCHARGE_TEMP_FIELD

 

 

 

 

 

 

 

 

 

 

information contained in nvoCtlDataG2 and nvoData2 are identical.

 

 

 

DISCHARGE_SET_PT_FIELD

 

 

 

 

 

 

 

 

 

 

nvoData2 is a polled network variable and must be polled by the receiver.

 

 

 

RETURN_TEMP_FIELD

 

 

 

 

 

 

 

 

 

 

nvoCtlDataG2 uses the SGPUC mechanism. FieldNo indicates which other

 

 

 

RETURN_HUMIDITY_FIELD

 

 

 

 

 

 

 

 

 

 

data field in the SGPUC network variable has changed since the last time it

 

 

 

RETURN_ENTHALPY_FIELD

 

 

 

 

 

 

 

 

 

 

was sent on the network according to the SGPUC mechanism.

 

 

 

OUTDOOR_TEMP_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR_HUMIDITY_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR_ENTHALPY_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILTER_PRESSURE_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE_CO2_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MONITOR_VOLTS_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL_POS_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT_POS_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECON_POS_FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPDATE_NO_FIELDS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BypTimer

nvoData2

uiBypassTimer

minutes

 

 

0

 

 

X

 

 

 

 

uiBypassTimer: The time left in the bypass timer is uiBypassTimer minutes.

 

(nvoCtlDataG2)

 

0 to 2880

 

 

 

 

 

 

 

 

 

 

If uiBypassTimer is zero, then the bypass timer is not running. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

uiBypassTimer is not zero, it is decremented every minute.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RmTempActSpt

nvoData2

siTempControlPtS7

Degrees F

 

 

SI_INVALID

 

 

X

 

 

 

 

siTempControlPtS7: The current temperature control point (such that, the

 

(nvoCtlDataG2)

 

50 to 85

 

 

 

 

 

 

 

 

 

 

current actual space temperature setpoint which the controller is presently

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

trying to maintain in the conditioned space) is calculated from the various

 

 

 

(10 to 29)

 

 

 

 

 

 

 

 

 

 

Setpoints, operating modes, network variable inputs, and optimum start-up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. The final result is stored in siTempControlPtS7.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RmTemp

nvoData2

siSpaceTempS7

Degrees F

 

 

SI_INVALID

 

 

 

 

 

 

 

siSpaceTempS7: siSpaceTempS7 is the space temperature used by the

 

(nvoCtlDataG2)

 

40 to 100

 

 

 

 

 

 

 

 

 

 

control process and is read from another node via nviSpaceTemp or a local

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

sensor via nvoIO.siSpaceTempS7 or nvoIO.siReturnTempS7. If the network

 

 

 

(4 to 38)

 

 

 

 

 

 

 

 

 

 

input is not SI_INVALID, then the network input has priority. The local

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sensor is selected by nciConfig.ControlUsesRtnAirTemp. When

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciConfig.ControlUsesRtnAirTemp is 0, then the space temperature sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is selected. When nciConfig.ControlUsesRtnAirTemp is 1, then the return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature sensor is selected. If the network input and the selected local

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sensor has failed or are not configured, siSpaceTempS7 is SI_INVALID.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 88
Image 88