Honeywell W7750A Modes of Operation, Dirty Filter Monitor, Indoor Air Quality IAQ Override

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 27
Image 27

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Dirty Filter Monitor

The air filter in the air handler can be monitored by the W7750 and an alarm is issued when the filter media needs replacement. The two methods of monitoring the filter are:

1.Connecting a differential pressure switch to a digital input on the W7750A or W7750B,C.

2.Wiring a 2 to 10V differential pressure sensor to a voltage input on the W7750B,C. If the analog input sensor is used, its measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a user-selectable setpoint (FltrPressStPt— valid range: 0 to 5 inw (0 to 1.25 kPa)), and the Dirty Filter alarm is issued when the pressure drop across the filter exceeds the setpoint.

Indoor Air Quality (IAQ) Override

The Excel 10 W7750 Controller provides IAQ ventilation control using one of two different methods of detecting poor air quality. The first is with an IAQ switch device connected to a digital input on the W7750 Controller, where a contact closure indicates poor air quality, and initiates the IAQ Override mode. The device can detect poor air quality using any desired measure such as CO2, VOC, CO, etc. The second method, which is only available on the W7750B,C, is through an analog input that connects to a CO2 sensor (2 to 10V). The measured value of CO2 from this sensor (0 to 2000 PPM) is compared to the setpoint (IAQSetpt). When the CO2 level is higher than the setpoint (800 PPM adjustable), the

IAQ Override is initiated. The IAQSetpt hysteresis is 50 PPM, IAQ Override is deactivated at a CO2 level less than 50 PPM below setpoint.

The effect of initiating the IAQ Override mode is that the economizer dampers are allowed to open above the standard minimum position setting to allow more fresh air to enter the building. See Appendix B— Sequences of Operation, for further control details.

Smoke Control

The Excel 10 W7750 Controller supports smoke-related control strategies that are initiated either via a network command (DestEmergCmd) or from a local (physically connected) smoke detector digital input. The details of the W7750 smoke-related control operation are described in Appendix B— Sequences of Operation.

Freeze Stat

A freeze stat can be monitored by the W7750 and issue a freeze stat alarm indicating the CVAHU is in danger of freezing its coil. The details of the W7750 freeze stat related control operation are described in Appendix B— Sequences of Operation.

Modes of Operation

The possible modes of operation for the W7750 Controller are listed in Table 5.

Table 5. Modes Of Operation For The Excel 10 W7750 Controller .

 

 

 

Mode

Description

Events causing a controller to switch to this mode

 

 

 

Effective Occupancy (User Address: StatusOcc)

 

 

 

 

OCCUPIED

Controller is in Occupied mode

Any of the following: Network input (DestSchedOcc) containing a

 

 

time-of-day schedule flag from either the Excel 10 Zone Manager or an

 

 

LONWORKS Bus Controller; Time Clock DI, Occupancy Sensor DI; or

 

 

from Network input (DestManMode) for manual override to OCC mode.

 

 

DestManMode has the highest priority, followed by the Time Clock DI,

 

 

and then DestSchedOcc.

 

 

 

STANDBY

Controller is in Standby mode

Either: (A) Network input (DestSchedOcc) containing a time-of-day

 

 

schedule flag from the Excel 10 Zone Manager or other LONWORKS

 

 

Bus node is STANDBY, or (B) Network input (DestSchedOcc) is

 

 

OCCUPIED and the Occupancy Sensor DI is UNOCCUPIED.

 

 

 

UNOCCUPIED

Controller is in Unoccupied mode

Network input (DestSchedOcc) containing a time-of-day schedule flag

 

 

from the Excel 10 Zone Manager or LONWORKS Bus, or the network

 

 

input DestManOcc has a value of UNOCCUPIED.

 

 

 

BYPASS

Controller is in Occupied mode through

This mode is derived from the schedule occupancy (DestSchedOcc)

OCCUPIED

a Bypass command

having a state of UNOCCUPIED and a manual request for occupancy

 

 

from one of three sources. Two of these are signals originated external

 

 

to the unit, and received by DestManOcc and DestBypass. The third

 

 

source for an occupancy request is from an override button located on

 

 

a wall module. These three sources are arbitrated in a scheme

 

 

determined by the configuration parameter (Network Wins or Last-in

 

 

Wins from OvrdPriority).

 

 

 

Override Modes (User Address: StatusOvrd)

 

 

 

 

OCCUPIED

Controller occupancy mode was

Network input (DestManOcc) containing a time-of-day schedule

 

overridden to Occupied mode

override signal of OCCUPIED from the Excel 10 Zone Manager or

 

 

other LONWORKS Bus device.

 

 

 

STANDBY

Controller occupancy mode was

Network input (DestManOcc) containing a time-of-day schedule

 

overridden to Standby mode

override signal of STANDBY from the Excel 10 Zone Manager or other

 

 

LONWORKS Bus device.

 

 

 

27

74-2958— 1

Page 27
Image 27
Honeywell W7750A Modes of Operation, Dirty Filter Monitor, Indoor Air Quality IAQ Override, Smoke Control, Freeze Stat