EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 9. Field Wiring Reference Table (Honeywell listed as AK#### or equivalent).

 

 

 

 

 

 

 

Recommended

 

Specification

 

 

Wire

Minimum Wire

 

or

 

Maximum Length ft.

Function

Size AWG (mm2)

Construction

Requirement

Vendor Wire Type

(m)

LONWORKS

22 AWG

Twisted pair solid

Level IV

Honeywell

Refer to LONWORKS Bus

Bus

(0.34 mm2)

conductor, nonshielded

140°F (60°C)

AK3791 (one twisted pair)

Wiring Guidelines for

(Plenum)

 

or Echelon approved

rating

AK3792 (two twisted pairs)

maximum length

 

 

cable.

 

 

 

 

 

 

 

 

 

LONWORKS

22 AWG

Twisted pair solid

Level IV

Honeywell

Refer to LONWORKS Bus

Bus (Non-

(0.34 mm2)

conductor, nonshielded

140°F (60°C)

AK3781 (one twisted pair)

Wiring Guidelines for

Plenum)

 

or Echelon approved

rating

AK3782 (two twisted pairs)

maximum length

 

 

cable.

 

 

 

 

 

 

 

 

 

Input

18 to 22 AWG

Multiconductor (usually

140°F (60°C)

Standard thermostat wire

1000 ft. (305m) for 18

Wiring

(1.0 to 0.34 mm2)

five-wire cable bundle).

rating

 

AWG 200 ft. (61m) for 22

Sensors

 

For runs >200 ft. (61m)

 

 

AWG

Contacts

 

in noisy EMI areas, use

 

 

 

 

 

shielded cable.

 

 

 

 

 

 

 

 

 

Output

14 AWG (2.0 mm2)

Any pair nonshielded

NEC Class 2

Honeywell

Limited by line-loss

Wiring

18 AWG (1.0 mm2)

(use heavier wire for

140°F (60°C)

AK3702 (18 AWG)

effects on power

Actuators

acceptable for

longer runs).

rating

AK3712 (16 AWG)

consumption. (See Line

Relays

short runs)

 

 

AK3754 (14 AWG)

Loss subsection.)

 

 

 

 

 

 

Power

14 AWG (2.0 mm2)

Any pair nonshielded

NEC Class 2

Honeywell

Limited by line-loss

Wiring

 

(use heavier wire for

140°F (60°C)

AK3754 (14 AWG) twisted

effects on power

 

 

longer runs).

rating

pair AK3909 (14 AWG)

consumption. (See Line

 

 

 

 

single conductor

Loss subsection.)

 

 

 

 

 

 

W7750 Controllers

Fig. 27 through 35 illustrate W7750A,B,C Controller wiring for various configurations. Connections to the wall module terminals (2 through 6) and the communications terminals (14 and 15) are made at terminal blocks. Connection for access to the LONWORKS Bus is provided by plugging the connector into the communications jack.

1.STRIP 1/2 IN. (13 MM)

1/2

FROM WIRES TO

BE ATTACHED AT

(13)

 

ONE TERMINAL.

2.TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM

OF THREE TURNS).

Q38

U3

J2

JUMPER

2

1 TERMINAL 24

3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)

BEFORE INSERTING INTO TERMINAL AND

 

TIGHTENING SCREW. THEN PULL ON EACH

WIRE IN ALL TERMINALS TO CHECK FOR

 

GOOD MECHANICAL CONNECTION.

M17207

 

Fig. 25. Attaching two or more wires at terminal blocks.

The W7750B provides a jumper to select High-Side or Low- Side switching of the digital outputs. Fig. 26 shows the W7750B High-Side/Low-Side selectable switching. (See wiring diagrams, Figs. 30 through 34.)

1J2 IS LOCATED NEAR TERMINAL 24 (COVER REMOVED).

2W7750B IS FACTORY-DELIVERED WITH JUMPER ON HIGH-SIDE

(PINS CLOSEST TO TERMINAL BLOCK). LOW-SIDE PINS ARE TWO

PINS CLOSEST TO Q38.

M16418A

Fig. 26. W7750B High-Side/Low-Side selectable switching

and jumper location.

NOTE: If an Excel 10 W7750A,B,C Controller or Zone Manager is not connected to a good earth ground, the controller internal transient protection circuitry is compromised and the function of protecting the controller from noise and power line spikes cannot be fulfilled. This can result in a damaged circuit board and require replacing the controller.

See Table 10 for a description of the W7750A terminals.

74-2958— 1

36

Page 36