Table 26. LONMARK® /Open System Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcEconEnCt

nvoEcon

value

0 to 100

 

0

 

X

 

 

 

 

 

nvoEcon allows one controller to determine the suitability of outdoor air for

 

(SNVT_switch)

 

 

 

 

 

 

 

 

 

 

 

free cooling and share this with other nodes and is typically bound to Econ

 

 

 

 

 

 

 

 

 

 

 

 

 

on other nodes. If the economizer function is configured by

 

 

 

 

 

 

 

 

 

 

 

 

 

Config.EconEnable, Econ is periodically calculated from the local sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

specified by Config.EconEnable and is sent on the network. Econ does not

 

 

 

 

 

 

 

 

 

 

 

 

 

affect Econ. The output has the following states: If the state is SW_OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

and the value is 0, then the outdoor air is not suitable for free cooling. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

state is SW_ON and the value is 100 percent, then the outdoor air is

 

 

 

 

 

 

 

 

 

 

 

 

 

suitable for free cooling. If the state is SW_NUL and the value is 0, the

 

 

 

 

 

 

 

 

 

 

 

 

 

corresponding economizer function is not enabled because

 

 

 

 

 

 

 

 

 

 

 

 

 

Config.EconEnable is ECON_NUL, DIFF_TEMP, or DIFF_ENTH or

 

 

 

 

 

 

 

 

 

 

 

 

 

because the selected sensor has failed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcEconEnable

nvoEcon

state

SW_OFF

0

SW_NUL

M

X

 

X

 

 

 

For nvoEcon.state, refer to nvoEcon.value.

 

(SNVT_switch)

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105