Honeywell W7750A StatusManOcc NvoData1 NetManOcc, Indicates that the space is bypass occupied for

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 85
Image 85

Table 23. Status Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

StatusManOcc

nvoData1

NetManOcc

OC_OCCUPIED

0

 

OC_NUL

 

 

X

 

 

 

 

NetManOcc: NetManOcc reports the network manual occupancy state from

 

 

(nvoCtlDataG1)

 

OC_UNOCCUPIED

1

 

 

 

 

 

 

 

 

 

nviManOcc. The valid enumerated states are: OC_OCCUPIED indicates

 

 

 

 

OC_BYPASS

2

 

 

 

 

 

 

 

 

 

occupied OC_UNOCCUPIED indicates not occupied OC_BYPASS

 

 

 

 

OC_STANDBY

3

 

 

 

 

 

 

 

 

 

indicates that the space is bypass occupied for

 

 

 

 

OC_NUL

255

 

 

 

 

 

 

 

 

nciAux2SetPt.uiBypassTime seconds after nviManOcc is first set to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_BYPASS OC_STANDBY indicates that the space is standby. OC_NUL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

means that no manual override is active.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusOcySen

nvoData1

SenOcc

OC_OCCUPIED

0

 

OC_NUL

 

 

X

 

 

 

 

SenOcc: SenOcc indicates the current state of the sensed occupancy and

 

 

(nvoCtlDataG1)

 

OC_UNOCCUPIED

1

 

 

 

 

 

 

 

 

 

is calculated from nviSensorOcc and the local occupancy sensor via

 

 

 

 

OC_BYPASS

2

 

 

 

 

 

 

 

 

 

nvoIO.OccupancySensor. The local sensor and nviSensorOcc are ORed

 

 

 

 

OC_STANDBY

3

 

 

 

 

 

 

 

 

 

together. If either the local sensor or nviSensorOcc shows occupancy, then

 

 

 

 

OC_NUL

255

 

 

 

 

 

 

 

 

SenOcc shows occupancy. The valid enumerated values are:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_OCCUPIED means that occupancy is sensed by one or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sensor.OC_UNOCCUPIED means that no occupancy is sensed by any

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sensors.OC_NUL means no local sensor is configured and nviSensorOcc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

has failed to be received periodically (bound or not bound).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusEconEn

nvoData1

EconEnable

ST_OFF

0

 

ST_NUL

 

 

X

 

 

 

 

EconEnable: EconEnable indicates the current suitability of outdoor air for

 

 

(nvoCtlDataG1)

 

ST_LOW

1

 

 

 

 

 

 

 

 

 

use in cooling used by the control process EconEnable is periodically

85

 

 

 

ST_MED

2

 

 

 

 

 

 

 

 

 

calculated either from the sensor(s) specified by nciConfig.EconEnable or

 

 

 

ST_HIGH

3

 

 

 

 

 

 

 

 

 

from nviEcon. When nviEcon.state is not SW_NUL, then the local inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST_ON

4

 

 

 

 

 

 

 

 

 

are ignored and nviEcon.state is used instead. See nciConfig.EconEnable.

 

 

 

 

ST_NUL

255

 

 

 

 

 

 

 

 

The valid enumerated values are: ST_OFF means the outdoor air is not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

suitable to augment cooling. ST_ON means the outdoor air is suitable to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

augment cooling.ST_NUL means no local sensor is selected by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciConfig.EconEnable, or the selected local sensor has failed or has not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

been configured by nciIoSelect, and that nviEcon.state is SW_NUL. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor air is considered unsuitable for cooling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SaFanStatus

nvoData1

ProofAirFlow

ST_OFF

0

 

ST_NUL

 

 

X

 

 

 

 

ProofAirFlow: ProofAirFlow indicates the current state of the ProofAirFlow

 

 

(nvoCtlDataG1)

 

ST_LOW

1

 

 

 

 

 

 

 

 

 

switch used by the control process and is read by the local sensor via

 

 

 

 

ST_MED

2

 

 

 

 

 

 

 

 

 

nvoIO.ProofAirFlow. The valid enumerated values are: ST_OFF means air

 

 

 

 

ST_HIGH

3

 

 

 

 

 

 

 

 

 

flow is not detected. ST_ON means air flow is detected. ST_NUL means no

 

 

 

 

ST_ON

4

 

 

 

 

 

 

 

 

 

air flow switch is configured.

 

 

 

 

ST_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OaEnthCalc

nvoData1

siCalcODEnthalpyS7

btu/lb

 

 

SI_INVALID

 

 

X

 

 

 

 

siCalcODEnthalpyS7: siCalcODEnthalpyS7 is the calculated outdoor air

 

 

(nvoCtlDataG1)

 

0 to 100

 

 

 

 

 

 

 

 

 

 

enthalpy in btu / lb calculated from the siOutdoorTempS7 and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ubOutdoorHumidityS1. siCalcODEnthalpyS7 is used to determine the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

suitability of outside air for cooling when nciConfig.EconEnable is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE_ENTH and both outdoor temperature and humidity sensors are

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

present. siCalcODEnthalpyS7 is compared to the enthalpy setpoint stored

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in nciAux1SetPts.ubOdEnthalpyEnableS2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RaEnthCalc

nvoData1

siCalcRAEnthalpyS7

btu/lb

 

 

SI_INVALID

 

 

X

 

 

 

 

siCalcRAEnthalpyS7: siCalcRAEnthalpyS7 is the calculated return air

 

 

(nvoCtlDataG1)

 

0 to 100

 

 

 

 

 

 

 

 

 

 

enthalpy in btu / lb calculated from the siReturnTempS7 and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ubReturnHumidityS1. siCalcRAEnthalpyS7 is used to determine the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

suitability of outside air for cooling when nciConfig.EconEnable is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIFF_ENTH and both outdoor and return (or space) temperature sensors

74-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and humidity sensors are present. Sensors may be physically connected to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the node or available over the network.

2958— 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 85
Image 85
Honeywell W7750A StatusManOcc NvoData1 NetManOcc, Indicates that the space is bypass occupied for, OaEnthCalc NvoData1