Honeywell W7750A HeatStgsOn NvoData1 HeatStagesOn, Auxiliary heating stages are turned on

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 86
Image 86

74-2958— 1

86

Table 23. Status Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

HeatStgsOn

nvoData1

HeatStagesOn

0 to 4

 

 

0

 

 

X

 

 

 

 

HeatStagesOn: HeatStagesOn indicates how many heating stages are on.

 

(nvoCtlDataG1)

 

 

 

 

 

 

 

 

 

 

 

 

If the node is controlling a heat pump, HeatStagesOn indicates how many

 

 

 

 

 

 

 

 

 

 

 

 

 

 

auxiliary heating stages are turned on.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CoolStgsOn

nvoData1

CoolStagesOn

0 to 4

 

 

0

 

 

X

 

 

 

 

CoolStagesOn: CoolStagesOn indicates how many compressor stages are

 

(nvoCtlDataG1)

 

 

 

 

 

 

 

 

 

 

 

 

on. If the node is controlling a heat pump, compressor stages are turned on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for both heating or cooling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Free1Stat

nvoData1

Free1Out

FALSE

0

 

FALSE

 

 

X

 

 

 

 

Free1Out: Free1Out indicates the state of FREE1_OUT digital output. 1

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

means on, and 0 means off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Free2Stat

nvoData1

Free2Out

FALSE

0

 

FALSE

 

 

X

 

 

 

 

Free2Out: Free2Out indicates the state of FREE2_OUT digital output. 1

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

means on, and 0 means off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OccStatOut

nvoData1

OccStatusOut

FALSE

0

 

FALSE

 

 

X

 

 

 

 

OccStatusOut: OccStatusOut indicates the state of the

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

OCCUPANCY_STATUS_OUT digital output. 1 means on (not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_UNOCCUPIED), and 0 means off (OC_UNOCCUPIED).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SaFan

nvoData1

FanOn

FALSE

0

 

FALSE

 

 

X

 

 

 

 

FanOn: FanOn indicates the state of the FAN_OUT digital output. 1 means

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

on, and 0 means off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusEconOut

nvoData1

AuxEconOut

FALSE

0

 

FALSE

 

 

X

 

 

 

 

AuxEconOut: AuxEconOut indicates the state of the AUX_ECON_OUT

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

digital output. 1 means that the packaged economizer is enabled, and 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

means the economizer is disabled. A packaged economizer is always

 

 

 

 

 

 

 

 

 

 

 

 

 

 

treated as the first stage of cooling when an economizer is configured by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoData1

EconFloatSynch

FALSE

0

 

FALSE

 

 

 

 

 

 

 

EconFloatSynch: EconFloatSynch indicates that the economizer damper

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

motor is being synchronized with the reported economizer position by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

driving the damper for a period longer than it takes to fully close the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damper. The reported economizer position is synchronized whenever an

 

 

 

 

 

 

 

 

 

 

 

 

 

 

endpoint is reached (full open or full close).and when the elapsed time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

since the last synchronization is 24 hours.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DlcShed

nvoData1

DlcShed

FALSE

0

 

FALSE

 

 

 

 

 

 

 

DlcShed: DlcShed indicates the state of nviDlcShed. When DlcShed is 1,

 

(nvoCtlDataG1)

 

TRUE

1

 

 

 

 

 

 

 

 

 

demand limit control set by an energy management node is active. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

effective occupancy is OC_OCCUPIED or OC_STANDBY when demand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

limit control is active, then the setpoint is shifted by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciAux1SetPt.siDlcBumpTempS7 in the energy saving direction. When

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DlcShed is 0, demand limit control is inactive. If nviDlcShed fails to be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

received periodically or nviDlcShed becomes 0, then the setpoint is ramped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

back to the original setpoint over a 30 minute interval.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 