Honeywell W7750A specifications Alarmnotifydisabled

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 102
Image 102

74-2958— 1

102

Table 26. LONMARK® /Open System Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoUnitStatus

in_alarm

FALSE

0

FALSE

 

 

 

 

 

 

 

When there is an alarm reported by AlarmStatus, then in_alarm is set to 1

 

(SNVT_hvac_status)

 

TRUE

1

 

 

 

 

 

 

 

 

(TRUE), else in_alarm is set to 0 (FALSE). If alarms reporting is

 

 

 

ALARM_NOTIFY_DISABLED

255

 

 

 

 

 

 

 

 

suppressed via ManualMode, then in_alarm is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARM_NOTIFY_DISABLED.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviInUse(unsigned

 

0 To 65535

 

0 to FFFF

 

 

 

 

 

 

 

InUse is used by a management node to indicate to all other management

 

long)

 

 

 

 

 

 

 

 

 

 

 

nodes that it is logged on to the Excel 10 node and that they should not try

 

 

 

 

 

 

 

 

 

 

 

 

 

to interact with any of the Excel 10s network variables. Before the

 

 

 

 

 

 

 

 

 

 

 

 

 

management node reads or writes any network variables, the management

 

 

 

 

 

 

 

 

 

 

 

 

 

node checks nviInUse for a zero value meaning no other management

 

 

 

 

 

 

 

 

 

 

 

 

 

nodes are already logged on and that a management node may log on to

 

 

 

 

 

 

 

 

 

 

 

 

 

the node. Then the management node writes a number, 1 through 65534,

 

 

 

 

 

 

 

 

 

 

 

 

 

to nviInUse and periodically writes the same value to indicate that the

 

 

 

 

 

 

 

 

 

 

 

 

 

management node is still logged on. If there are no writes made to

 

 

 

 

 

 

 

 

 

 

 

 

 

nviInUse for approximately 60 seconds, then the Excel 10 resets nviInUse

 

 

 

 

 

 

 

 

 

 

 

 

 

to zero to automatically log off the management node. Before interacting

 

 

 

 

 

 

 

 

 

 

 

 

 

with any network variables, the management node verifies that the

 

 

 

 

 

 

 

 

 

 

 

 

 

nviInUse has not changed. The management node logs off by writing 0 to

 

 

 

 

 

 

 

 

 

 

 

 

 

nviInUse.During power up, an application restart, or return to on-line from

 

 

 

 

 

 

 

 

 

 

 

 

 

off-line, the Excel 10 sets InUse to 65535 to indicate to the management

 

 

 

 

 

 

 

 

 

 

 

 

 

node that it has returned to on-line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

object_id

0 to 65535

 

0

M

 

 

X

 

 

 

object_id is set to the current value of nviRequest.object_id

 

(SNVT_obj_request)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

invalid_id

FALSE

0

FALSE

 

 

 

 

 

 

 

If Request.Object_id is not a valid object, invalid_id is set to 1 (TRUE)

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

otherwise it is set to 0 (FALSE).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

invalid_request

FALSE

0

FALSE

 

 

 

 

 

 

 

If Request.object_request is not a valid request for the object addressed,

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

invalid_request is set to 1 (TRUE) otherwise it is set to 0 (FALSE).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

disabled

FALSE

0

FALSE

 

 

 

 

 

 

 

The disabled field is not supported and is set to 0 (FALSE) unless

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

Request.object_request is RQ_REPORT_MASK, then disabled and

 

 

 

 

 

 

 

 

 

 

 

 

 

in_alarm are set to 1 (TRUE) to indicate that these functions are supported

 

 

 

 

 

 

 

 

 

 

 

 

 

while all other fields are set to 0 (FALSE).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

out_of_limits

FALSE

0

FALSE

 

 

 

 

 

 

 

The out_of_limits field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

open_circuit

FALSE

0

FALSE

 

 

 

 

 

 

 

The open_circuit field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

out_of_service

FALSE

0

FALSE

 

 

 

 

 

 

 

The out_of_service field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

mechanical_fault

FALSE

0

FALSE

 

 

 

 

 

 

 

The mechanical_fault field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

feedback_failure

FALSE

0

FALSE

 

 

 

 

 

 

 

The feedback_failure field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

over_range

FALSE

0

FALSE

 

 

 

 

 

 

 

The over_range field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoStatus

under_range

FALSE

0

FALSE

 

 

 

 

 

 

 

The under_range field is not supported and is set to 0 (FALSE).

 

(SNVT_obj_request)

 

TRUE

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 102
Image 102
Honeywell W7750A specifications Alarmnotifydisabled