EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Common Operations

NOTE: Each W7750 Controller must have a space

The Excel 10 W7750 Controller applications have many

temperature sensor input either wired directly to the

controller, or shared from another LONWORKS Bus

common operations that are applicable regardless of the type

device, and must have a digital output configured for

of heating, cooling, or economizer equipment configuration.

controlling the supply fan. In addition, if modulating

These operations are available to the W7750A and the

economizer control is desired, a discharge air

W7750B,C Versions of the CVAHU Controller, and the I/O and

temperature sensor must be physically connected to

network configurations for them are summarized in Table 14.

the Excel 10 W7750 Controller. A discharge

 

Available input options are from the wall module and the

temperature signal cannot be brought into the

controller through the LONWORKS Bus network.

hard-wired analog and digital inputs. Each application can

 

have only a subset of these devices configured based on the

 

number of physical I/O points available. However, some of the

 

inputs are available over the LONWORKS Bus network.

 

Table 14. Common Configuration Options Summary For W7750A,B,C Controllers.

 

 

 

Option

 

Possible Configurations Common To All W7750 Models

 

 

 

Supply Fan

1.

Mandatory Digital Output.

 

 

 

Type of Air Handler

1.

Conventional.

 

 

 

 

2.

Heat Pump.

 

 

 

Occupancy Sensor

1.

None.

 

 

 

 

2.

Connected: Contacts closed equals Occupied.

 

 

 

 

3.

Network (Occ/Unocc signal received via the LONWORKS Bus network).

 

 

 

Window Sensor

1.

None.

 

 

 

 

2.

Physically Connected: Contacts closed equals window closed.

 

 

 

 

3.

Network (Window Open/Closed signal received via the LONWORKS Bus).

 

 

 

Wall Module Option

1.

Local (direct wired to the controller).

 

 

 

(The T77560A,B has no LONWORKS Bus access)

2.

Network (sensor value received via the LONWORKS Bus).

 

 

 

Wall Module Type

1.

Sensor only.

 

 

 

(All wall modules have a LONWORKS Bus access

2.

Sensor and Setpoint adjust.

 

 

 

jack except T7560A,B)

3.

Sensor, Setpoint adjust and Bypass.

 

 

 

 

4.

Sensor and Bypass.

 

 

 

Smoke Emergency Initiation

1.

None.

 

 

 

 

2.

Physically Connected: Contacts closed equals smoke detected.

 

 

 

 

3.

Network (Emergency/Normal signal received via the LONWORKS Bus).

 

 

 

53

74-2958— 1

Page 53