Honeywell W7750A MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr, MaxClRamp, OdTempMaxClRamp

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 75
Image 75

 

 

 

 

 

Table 21. Control Parameters. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

MaxClRamp

nciAux1SetPt

ubMaxClRampS0

Degrees F/Hr

 

 

 

6

P

 

X

X

 

 

 

MaxClRamp is the maximum cool recovery ramp rate in degrees F

 

 

 

 

0 to 20

 

 

 

 

 

 

 

 

 

 

 

per hour. This value is used to control the adaptive recovery ramp

 

 

 

 

Degrees C/Hr

 

 

 

 

 

 

 

 

 

 

 

rate during the COOL recovery period. The setpoint is changed at a

 

 

 

 

(0 to 11)

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MinClRamp, OdTempMaxClRamp, and OdTempMinClRamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. If there is no outdoor air temperature sensor available,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then MinClRamp is used as the recovery rate. Refer to the NOTE in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the comments column for MaxHtRamp for the conditions that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MinClRamp

nciAux1SetPt

ubMinClRampS0

Degrees F/Hr

 

 

 

2

P

 

X

X

 

 

 

MinClRamp is the minimum cool recovery ramp rate in degrees F

 

 

 

 

0 to 20

 

 

 

 

 

 

 

 

 

 

 

per hour. This value is used to control the adaptive recovery ramp

 

 

 

 

Degrees C/Hr

 

 

 

 

 

 

 

 

 

 

 

rate during the COOL recovery period. The setpoint is changed at a

 

 

 

 

(0 to 11)

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MaxClRamp, OdTempMaxClRamp, and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OdTempMinClRamp parameters. If there is no outdoor air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature sensor available, then MinClRamp is used as the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery rate. Refer to the NOTE in the comments column for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MaxHtRamp for the conditions that recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

OaTempMaxClRp

nciAux1SetPt

ubOdTempMaxClRampS0

Degrees F

 

 

 

70

P

 

X

X

 

 

 

OdTempMaxClRamp is the maximum outdoor air temperature

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

 

parameter that is used to calculate the cool recovery ramp rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

setpoint. This value is used to control the adaptive recovery ramp

 

 

 

 

(-18 to 38)

 

 

 

 

 

 

 

 

 

 

 

rate during the COOL recovery period. The setpoint is changed at a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MaxClRamp, MinClRamp, and OdTempMinClRamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. If there is no outdoor air temperature sensor available,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then MinClRamp is used as the recovery rate. Refer to the NOTE in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the comments column for MaxHtRamp for the conditions that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OaTempMinClRp

nciAux1SetPt

ubOdTempMinClRampS0

Degrees F

 

 

 

90

P

 

X

X

 

 

 

OdTempMinClRamp is the minimum outdoor air temperature

 

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

 

parameter that is used to calculate the cool recovery ramp rate

 

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

setpoint. This value is used to control the adaptive recovery ramp

 

 

 

 

(-18 to 38)

 

 

 

 

 

 

 

 

 

 

 

rate during the COOL recovery period. The setpoint is changed at a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MaxClRamp, MinClRamp, and OdTempMaxClRamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. If there is no outdoor air temperature sensor available,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then MinClRamp is used as the recovery rate. Refer to the NOTE in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the comments column for MaxHtRamp for the conditions that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OaEconEnTemp

nciAux1SetPt

ubOdEconEnableTempS0

Degrees F

 

 

 

70

P

 

X

X

 

 

 

If Config.EconEnable is OD_TEMP, and the outdoor temperature is

 

 

 

 

0 to 90

 

 

 

 

 

 

 

 

 

 

 

less than OdEconEnableTemp, then outdoor air is judged suitable to

 

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

augment mechanical cooling. If Config.EconEnable is

 

 

 

 

(-18 to 32)

 

 

 

 

 

 

 

 

 

 

 

SINGLE_ENTH and outdoor temperate is less than

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ubOdEconEnableTemp (high limit), then outdoor air may be judged

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

suitable to augment mechanical cooling depending on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relationship between calculated outdoor enthalpy and

74-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OdEnthalpyEnable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DiffEconEnTemp

nciAux1SetPt

ubDiffEconEnableTempS0

Degrees F

Degrees C

 

 

4

P

 

X

X

 

 

 

If Config.EconEnable is DIFF_TEMP, and return air temperature

2958

 

 

 

0 to 90

(-18 to 32)

 

 

 

 

 

 

 

 

 

 

minus outdoor air temperature is greater than DiffEconEnableTemp,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then outdoor air is judged suitable to augment mechanical cooling.

— 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 75
Image 75
Honeywell W7750A MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr, MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr