Juniper Networks G10 CMTS manual AC Power

Models: G10 CMTS

1 210
Download 210 pages 10.01 Kb
Page 87
Image 87

Power

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

(1) This device may not cause harmful interference, and

(2)this device must accept any interference received, including interference that may cause undesired operation.

Power

The G10 CMTS can be configured with either AC or DC power supply modules. To support a fully-populated CMTS, the installation site must be able to source 1500 watts of input power.

The G10 CMTS chassis midplane is electrically partitioned into A and B domains. To support power redundancy, you must supply power from different circuits to each power transition module to implement power source redundancy.

Ensure that all power distribution panel switches on the rear of the CMTS are in the off position prior to connecting any electrical power cords. Also ensure that the CMTS chassis is properly grounded to earth prior to connecting any source of power.

AC Power

The G10 CMTS requires an AC power source that operates within a voltage and frequency range of 100 to 240 VAC and 47 to 63 Hz. In addition, appropriately sized circuit protection measures must be implemented to ensure compliance with electrical regulatory standards.

Use the factory-supplied power cords for AC power.

AC power sources must use circuit breakers, rather than fuses, for current surge protection.

Prepare the Site