Kentrox AI232 manual Alarm, Command Type shell Formats

Models: AI232

1 322
Download 322 pages 30.19 Kb
Page 192
Image 192

AI232 Version 9.6x User’s Guide

AI232 Commands: alarm

alarm

Description

This command:

zDisplays a list of the alarm groups and the overall alarm severity

zDisplays alarms for a specified alarm group or for a specified range of severity levels within an alarm group

zDisplays alarms by severity level or for a specified range of severity levels

zClears all non-self-clearing alarm groups and the overall alarm severity

zClears a specified non-self-clearing alarm group

zMasks a specified alarm group

zUnmasks a specified alarm group.

Command Type shell

Formats

alarm [ group [ range ] ] alarm -sev[ range ]

alarm { -clear [ group ] -mask group -unmask group }

Parameters

group

Defines the group of alarms to display, clear, mask, or unmask. Valid

 

values are existing alarm groups.

range

Defines a range of alarm severity levels to display. Valid values are 1 to

 

32. Individual values in the range are separated by hyphens (-).

-sev

Displays all alarms or a range of alarms based severity level.

-clear

Clears all non-self-clearing alarm groups or a specified non-self-clearing

 

alarm group.

 



 

Note: Only non-self-clearing alarm groups can be manually cleared.

 

Self-clearing alarms clear themselves when the problem that

 

caused the alarm is resolved.

-mask

Prevents a specified alarm group from affecting overall alarm severity.

-unmask

Allows a specified alarm group to affect overall alarm severity.

8-20

Page 192
Image 192
Kentrox AI232 manual Alarm, Command Type shell Formats