Mail Send Function Errors

Section 2-8

 

 

 

 

Cause

Correction

 

 

 

 

Details of trigger setting error

Correctly set the trigger type setting.

 

 

 

 

Specified word or specified bit data area/

Correctly set the data area and address

 

address error

for the specified word or bit.

2-8-2 Troubleshooting Mail Send Errors with LED Indicators

RUN

ERC

ERH

LNK

HOST

Probable cause

Correction

 

 

 

 

 

 

 

Lit

---

Lit

---

Flashing

There is an error in the server

Read the Error Status Flags and

 

 

 

 

 

(DNS, SMTP, or POP3) settings in

error log and correct the setting

 

 

 

 

 

the Unit Setup.

that caused the error. If the error

 

 

 

 

 

 

recurs, replace the CPU Unit.

 

 

 

 

 

 

 

 

 

Not lit

---

Flashing

• An authentication error occurred

• Correctly set the POP settings

 

 

 

 

 

in “POP before SMTP” authenti-

(account and password).

 

 

 

 

 

cation. A communications prob-

• Inspect the communications path

 

 

 

 

 

lem occurred with the server.

(Ethernet Unit, cable connec-

 

 

 

 

 

• A network failure occurred in the

tions, hub, router, and server)

 

 

 

 

 

communications path and

and correct any problems or

 

 

 

 

 

caused an access timeout.

damage.

 

 

 

 

 

 

 

Note For more details on the error log, refer to 8-3 Error Log in the Operation Man- ual Construction of Networks (W420).

2-8-3 Error Log Error Codes for the Mail Send Function

When an error occurs while the Ethernet Unit is operating, the error code, detailed error code, and time the error occurred are saved in the error log. The following table provides a list of the error codes.

The error log can be read by sending FINS commands to the Ethernet Unit or by using the mail receive function and specifying the ErrorLogRead com- mand.

Error

Meaning

Detailed error code

Correction

EEPROM

code

 

 

 

 

 

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

021A

Logic error

00

01: Data link

Recreate the data

Saved

 

in setting

 

table

specified by the

 

 

table

 

02: Network

2nd byte of the

 

 

 

 

detailed error

 

 

 

 

parameters

 

 

 

 

code.

 

 

 

 

03: Routing

 

 

 

 

 

 

 

 

 

tables

 

 

 

 

 

04: Setup

 

 

 

 

 

05: CPU Bus

 

 

 

 

 

Unit Words

 

 

 

 

 

(CIO/DM)

 

 

29

Page 53
Image 53
Omron CJ1W-ETN21 Troubleshooting Mail Send Errors with LED Indicators, Error Log Error Codes for the Mail Send Function