Using Socket Services by Manipulating Dedicated Control Bits

Section 6-7

If the Remote IP Address is set to 0, a connection can be made to any remote node and the remote IP address of the node that is connected will be stored as the Remote IP Address in the Socket Service Parameter Area. If a specific remote I/O address is set, then a connection can be made only to the node with the specified address.

If the Remote TCP Port No. is set to 0, a connection can be made to any remote node regardless of the TCP port number it is using. If a specific remote TCP port number is set, then a connection can be made only to a node using the specified TCP port number.

Remote UDP/TCP Port No.

Specify the UDP or TCP port number used by the remote device.

This parameter is not used when making a receive request for a UDP socket. The remote UDP/TCP port number will be stored with the response data and will be written as the Remote UDP/TCP Port No. in the Socket Service Parameter Area.

When opening a passive TCP socket, the combination of the remote IP address and the remote TCP port number can be used to affect process- ing as shown in the table for the Remote IP Address, above. If the Remote UDP/TCP Port No. is set to 0, the UDP/TCP port number of the remote device will be written as the Remote UDP/TCP Port No. in the Socket Ser- vice Parameter Area.

Time Out Time

Set the time limit in units of 0.1 s for completion of communications from the time that the Receive Request Switch (TCP or UDP) or the TCP Passive Open Request Switch is turned ON. A response code of 0080 hexadecimal (timeout) will be stored if communications time out. If 0 is set, the requested service will not be timed.

Number of Bytes to Send/Receive

Send the number of bytes to be sent or the number of bytes to receive. When the transfer has been completed, the actual number of bytes that have been sent or received will be written here.

Send/Receive Data Address

Specify the address of the first word to send or the address of the first word where data is to be received. Always set the bit number to 00 hexadecimal.

Offset

+6

+7

15

8

7

0

 

Area

 

Leftmost 2 digits

 

designation

 

of word address

 

 

 

 

 

Rightmost 2 digits

 

Bit number

 

of word address

 

(always 00 Hex)

The following specifications can be used.

 

Area

Word address

Area

Word address

 

 

 

 

designation

(hexadecimal)

 

 

 

 

(hexadecimal)

 

 

 

 

 

 

 

CIO, HR,

 

CIO

0000 to 6143

B0

0000 to 17FF

and AR

 

 

 

 

 

 

HR

H000 to H511

B2

0000 to 01FF

Areas

 

 

 

 

 

 

 

AR

A448 to A959

B3

01C0 to 03BF

 

 

 

 

 

 

 

 

DM Area

 

DM

D00000 to D32767

82

0000 to 7FFF

 

 

 

 

 

 

EM Area

 

Bank 0

E0_00000 to E0_32767

A0

0000 to 7FFF

 

 

:

:

:

:

 

 

Bank C

EC_00000 to EC_32767

AC

0000 to 7FFF

 

 

 

 

 

 

118

Page 142
Image 142