Mail Send Function Status

 

Section 2-5

 

 

 

 

 

Item

Contents

Default

 

 

 

 

 

CPU condition

If this option is selected, mail is sent whenever

Not selected

 

 

any of the following conditions occur at the CPU

 

 

 

Unit.

 

 

 

Use the drop-down list at the right to select one

 

 

 

of the following three conditions as the mail trig-

 

 

 

ger.

 

 

 

• When a non-fatal error occurs

 

 

 

• When a fatal error occurs

 

 

 

• When the operating mode is changed

 

 

 

 

 

 

Periodic timer

If this option is selected, an e-mail is sent at

Not selected

 

 

fixed time intervals. The time interval is set in 10-

 

 

 

minute units in the Interval time box. (The mini-

 

 

 

mum interval is 10 minutes.)

 

 

 

 

 

Note The Area and Address setting ranges are as follows:

CIO Area: 0 to 6143; Work Area: W000 to W511; Holding Area: H000 to

H511; Auxiliary Area: A000 to A447; Timer PVs: T0000 to T4095; Counter

PVs: C0000 to C4095; DM Area: D00000 to D32767; EM Area: 0 to 32767 in each bank

Interval Time Setting

(For Periodic timer, Word value change, and Bit value change Triggers)

 

 

 

 

 

 

Item

 

Contents

Default

 

 

 

 

 

 

Interval time

Periodic timer

Sets the time interval between

Selected

 

 

selected as the

e-mails.

 

 

 

trigger type

1 to 1,440 (10 to 14,400 min-

 

 

 

 

utes)

 

 

 

 

Units: 10-minute units

 

 

 

 

Default: 0000

 

 

 

 

 

 

 

 

Word value

Sets the interval at which the

 

 

 

change or Bit

word/bit contents are com-

 

 

 

value change

pared.

 

 

 

selected as the

1 to 1,000 (1 to 1,000 s)

 

 

 

trigger type

Units: 1 s

 

 

 

 

Default: 0000

 

 

 

 

 

 

2-5 Mail Send Function Status

2-5-1 Send Mail Status

The following two Send Mail Status words are located in the DM Area words allocated to the Ethernet Unit as a CPU Bus Unit.

The leading address (m) of the allocated DM area depends on the Ethernet

Unit's unit number (m = D30000 + 100 unit number).

Send Mail Status 1

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

m

Status of Send Condition Setting 1

Status of Send Condition Setting 2

Status of Send Condition Setting 3

Status of Send Condition Setting 4

24

Page 48
Image 48
Omron CJ1W-ETN21 operation manual Mail Send Function Status, Send Mail Status