Using the Automatic Clock Adjustment Function

Section 5-2

5-2-3 Auto Adjust Time

The contents in the CPU Bus Unit System Setup that are set for using mail send and receive functions are shown in the CX-Programmer’s Unit Setup.

Item

Contents

Default

 

 

 

Get the time

Enable to set the CPU Unit's clock to the time at the

Not

information from

SNTP server's clock.

selected

the SNTP

The clock can be changed only for the CPU Unit to

(disabled)

server

 

which the Ethernet Unit is mounted.

 

 

 

 

 

 

Auto Adjust

Set the time at which the SNTP server is to be

0:0:0

Time

accessed to synchronize the clocks.

 

 

When the time that is set here arrives, the SNTP

 

 

server is accessed and the CPU Unit clock is

 

 

adjusted to match the SNTP server clock.

 

 

 

 

Server specifi-

Select whether the SNTP server used for automatic

IP Address

cation type

clock adjustment is to be specified by IP address or

 

 

by host domain name (i.e., by host name).

 

 

 

 

IP Address

Set the IP address for the SNTP server that is to be

0.0.0.0

 

used for automatic clock adjustment.

 

 

This setting is enabled only when server specification

 

 

by IP address has been selected.

 

 

 

 

Host name

Set the host domain name (i.e., the host name) for

None

 

the SNTP server that is to be used for automatic

 

 

clock adjustment.

 

 

This setting is enabled only when server specification

 

 

by host name has been selected.

 

 

 

 

Port No.

Set the port number for connecting to the SNTP

0

 

server that is to be used for automatic clock adjust-

(Number

 

ment. This setting does not normally need to be

123 is

 

changed.

used.)

 

 

 

Retry timer

Set the time to elapse before retrying when a connec-

0

 

tion to the SNTP server fails. This setting does not

(10 s)

 

normally need to be changed.

 

 

 

 

Adjust Time

This sets in the CPU Unit's clock data the time differ-

+0:0

 

ence made up from the SNTP server's clock data.

 

 

To use the clock data from the SNTP server just as it

 

 

is, input 0.

 

 

 

 

93

Page 117