Omron CJ1W-ETN21 operation manual Response E-mail

Models: CJ1W-ETN21

1 242
Download 242 pages 30.9 Kb
Page 61
Image 61

Mail Receive Function Specifications

Section 3-2

 

 

 

 

 

 

Item

 

Specification

 

 

 

 

 

 

Attached

 

Data format

• IOM Write command:

 

file

 

 

Writes an I/O memory data file (IOM, TXT, or CSV) to the CPU Unit.

 

 

 

 

• File Write command:

 

 

 

 

Any type of file (a file with any filename extension) can be written to EM file memory or a

 

 

 

Memory Card mounted in the CPU Unit.

 

 

 

 

 

 

 

 

 

Data size

• IOM Write command: 6,000 words max. (same limit for all file types)

 

 

 

 

• File Write command: 1 MB max.

 

 

 

 

 

 

 

 

 

Format

MIME (version 1.0) format

 

 

 

 

 

 

 

 

 

Number of

Only one file

 

 

 

attachments

If more than one file is received, only the first file will be received and the remaining files will be

 

 

 

 

 

 

discarded.

 

 

 

 

 

 

 

Reception

 

Subject: Us ASCII

 

(decoding)

 

Body: Us ASCII

 

 

 

 

Attached file: Base64, quoted printable, 7 bit

 

 

 

 

Note Only one attached file is allowed. The filename must be ASCII and up to 8 + 3 charac-

 

 

 

 

ters long.

 

 

 

 

 

 

Encryption

 

None

 

 

 

 

 

Compression

None

 

 

 

 

Command line

Body: Data can be entered. (Lines other than the parameter line are comment lines.)

 

 

 

Attached file: Cannot be entered.

 

 

 

 

 

 

Protection

 

Protections when reading mail:

 

 

 

 

 

Authentication by password.

 

 

 

 

Protections when receiving remote mail commands:

 

 

 

 

 

The following protections can be used.

 

 

 

 

1. Receive from specified mail address only.

 

 

 

 

2. Receive attached files with the specified filename extensions only.

 

 

 

 

3. Restrict the remote mail commands that will be accepted.

 

 

 

 

 

 

Response E-mail

 

 

 

 

 

 

 

 

 

 

 

Item

 

Specification

 

 

 

 

Protocol used

 

SMTP (Port number: 25/TCP; can be changed in the CPU Bus Unit Setup using the CX-

 

 

 

 

Programmer.)

 

 

 

 

 

(The Use POP before SMTP Option can be selected to authenticate account and pass-

 

 

 

 

word information with the "POP before SMTP" method.)

 

 

 

 

 

 

Subject

 

 

The remote mail command is automatically entered after "Re:".

 

 

 

 

 

Example: Re: FileRead

 

 

 

 

E-mail body

 

Contains the response code and response status (fixed text associated with the response

 

 

 

 

code).

 

 

 

 

 

 

Attached

 

Data format

 

• IOM Read command:

 

file

 

 

 

Reads data from the CPU Unit and creates an I/O memory data file (IOM, TXT, or CSV).

 

 

 

 

• File Read command:

 

 

 

 

 

Any type of file (a file with any filename extension) can be read from EM file memory or a

 

 

 

 

Memory Card mounted in the CPU Unit.

 

 

 

 

 

 

 

 

 

Data size

 

• IOM Read command: 6,000 words max. (same limit for all file types)

 

 

 

 

 

• File Read command: 1 MB max.

 

 

 

 

 

 

 

 

 

Format

 

MIME (version 1.0) format

 

 

 

 

 

 

 

 

Number of attach-

Only one file

 

 

 

ments

 

 

 

 

 

 

 

 

 

Response

 

 

Subject: Us ASCII

 

(encoding)

 

 

Body: Us ASCII

 

 

 

 

 

Attached file: Base64

 

 

 

 

 

 

Encryption

 

 

None

 

 

 

 

 

Compression

 

None

 

 

 

 

 

 

 

37

Page 61
Image 61