Example Application

 

 

 

Section 2-9

 

 

 

 

 

 

 

 

Error

Meaning

Detailed error code

Correction

EEPROM

 

code

 

 

 

 

 

 

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03C1

Server set-

00: DNS

01: IP address

Set the server

---

 

 

ting error

01: SMTP

02: Host name

settings correctly

 

 

 

 

based on the

 

 

 

 

02: POP3

03: Port number

 

 

 

 

information in the

 

 

 

 

03: SNTP

04: Other

detailed error

 

 

 

 

 

parameters

code.

 

 

 

 

 

 

 

 

 

03C4

Server

00: DNS

01: Specified

Take either of the

---

 

 

connection

01: SMTP

host does not

following mea-

 

 

 

error

02: POP3

exist

sures.

 

 

 

 

03: SNTP

02: No service

• Correct the set-

 

 

 

 

at specified host

tings for each

 

 

 

 

 

03: Timeout

server.

 

 

 

 

 

• Inspect the com-

 

 

 

 

 

04: Closed uni-

 

 

 

 

 

munications

 

 

 

 

 

laterally by host

 

 

 

 

 

path (Ethernet

 

 

 

 

 

05: Cannot con-

 

 

 

 

 

Unit, cable con-

 

 

 

 

 

nect because

 

 

 

 

 

nections, hub,

 

 

 

 

 

account infor-

 

 

 

 

 

router, server),

 

 

 

 

 

mation does not

 

 

 

 

 

and correct the

 

 

 

 

 

match

 

 

 

 

 

situation that is

 

 

 

 

 

06: Host name

 

 

 

 

 

causing the

 

 

 

 

 

resolution error

error.

 

 

 

 

 

07: Transmis-

 

 

 

 

 

 

sion error

 

 

 

 

 

 

08: Reception

 

 

 

 

 

 

error

 

 

 

 

 

 

09: Other error

 

 

 

 

 

 

 

 

 

Note For more details on the error log, refer to 8-3 Error Log in the Operation Man- ual Construction of Networks (W420).

2-9 Example Application

2-9-1 Step 1. Create the I/O Table

Mount the Ethernet Unit in the CPU Rack or Expansion Rack, connect online with the CX-Programmer or Programming Console, and create the I/O table.

2-9-2 Step 2. Make the Unit Setup Settings from the CX-Programmer

With the CX-Programmer connected online, select the Ethernet Unit in the CX-Programmer's PLC I/O Table Window, right-click and select Unit Setup from the popup menu. Make the following settings in the CPU Bus Unit Setup Area from the CPU Bus Unit Setup Window.

1. Initial Settings (Example)

Initial Server Settings

Tab

Item

Setting

 

 

 

SMTP

Server specification type

Host Name

 

 

 

 

Host name

smtp.omron.com

 

 

 

 

Port No.

25 (default value)

 

 

 

 

Local mail address

ETN21@omron.co.jp

 

 

 

 

Use POP before SMTP

Not selected

 

 

 

30

Page 54
Image 54
Omron CJ1W-ETN21 Example Application, Create the I/O Table, Make the Unit Setup Settings from the CX-Programmer