LRS-24Installation and Operation Manual

Appendix B LRS-PS-FEED Power Supply

 

 

DC Power

DC-powered LRS-PS-FEED units require a –48 VDC power source.

Note No power switch is provided for the DC power supply modules, and therefore it is recommended to connect the DC power to the LRS-PS-FEED through a circuit breaker located close to the LRS-PS-FEED, that will also permit turning off the power to the LRS-PS-FEED.

Grounding

For your protection and to prevent possible damage to equipment when a fault condition (e.g., lightning stroke or contact with high-voltage power line) occurs

on the lines connected to the equipment, the LRS-PS-FEED case must be Warning properly grounded at all times. Never connect cables to an LRS-PS-FEED that is

not properly grounded.

Any interruption of the protective (grounding) connection inside or outside the equipment, or the disconnection of the protective ground terminal makes this equipment dangerous. Intentional interruption is prohibited.

Before switching on this equipment and before connecting any other cable, connect the protective ground terminal of the enclosure to a protective ground.

LRS-PS-FEED units are grounded through the protective (grounding) conductor of the power cable.

When LRS-PS-FEED is installed in racks, the rack itself should also be grounded in accordance with standard practice and the locally applicable regulations. Installing the unit in a grounded rack provides additional protection against fault conditions.

Front Clearance

Allow at least 90 cm (36 inches) of frontal clearance for operator access.

Ambient Requirements

The ambient operating temperature of the LRS-PS-FEED should be 32° to 113°F (0° to 45° C), at a relative humidity of up to 90%, non-condensing.

Cooling

LRS-PS-FEED units are cooled by free air convection. The cooling vents are located in the top and bottom covers. Do not obstruct these vents. Allow at least 1U of space below and above the unit.

Site Requirements