13. Appendix F: Modbus Commands
Code | Name of the | Description of the exception | |
exception | |||
|
| ||
16#01 | ILLEGAL FUNCTION | The query’s “Function” command code is not implemented in the Modbus slave | |
|
| software, or it is unable to process it for the moment. | |
16#02 | ILLEGAL DATA | The combination of the query’s “Starting Address” and “No. of Registers” fields | |
| ADDRESS | (or assimilated fields) gives access to one or more addresses which are not | |
|
| accessible on the Modbus slave. | |
16#03 | ILLEGAL DATA | The value of one of the Modbus query’s fields is outside the authorized limits. | |
| VALUE | This error does not affect the content of the “Data” (or assimilated) fields, as this | |
|
| error only takes account of the fields used for managing the Modbus protocol. | |
16#04 | SLAVE DEVICE | An unrecoverable failure has occurred when processin the command. | |
| FAILURE | ||
|
| ||
16#05 | ACKNOWLEDGE | The Modbus slave informs the gateway that it has accepted the command | |
(1) |
| (acknowledgement), but that it will take too long to process it and it cannot afford | |
|
| to wait for the completion of this process before sending a response. | |
|
| The gateway should transmit subsequent queries in order to determine whether | |
|
| the command has finished or not. | |
16#06 | SLAVE DEVICE | The Modbus slave informs the gateway that it is already in the process of | |
(1) | BUSY | running a command and therefore it cannot run the one transmitted to it. | |
|
| So the gateway should | |
16#07 | NEGATIVE | The Modbus slave informs the gateway that it cannot process the requested | |
(1) | ACKNOWLEDGE | command. This exception only affects commands 13 and 14 (16#0D and | |
|
| 16#0E). These functions are not part of the standard Modbus commands and are | |
|
| not described in this document. | |
16#08 | MEMORY PARITY | The Modbus slave informs the gateway that it has detected a parity error on the | |
(1) | ERROR | access to its own memory. This exception only affects standard commands 20 | |
|
| and 21 (16#14 and 16#15) which are not supported by the gateway. |
(1) Please see the standard Modbus documentation for further information about these various scenarios.
112