Schneider Electric LUFP7 user manual Default communication mode. The query is transmitted

Models: LUFP7

1 115
Download 115 pages 53.73 Kb
Page 74
Image 74

6. Configuring the Gateway

Configuration

Description

 

element

 

 

 

Update mode

This element is used to specify the transmission mode for the query on the Modbus

 

network. It takes one of the following four values:

 

- Cyclically

Default communication mode. The query is transmitted

 

periodically on the Modbus network (see “Update time”).

 

- On data change

The gateway transmits the query on the Modbus network

 

when at least one item of data from this query is changed by the Profibus-DP master.

 

So this is an aperiodic communication mode. For instance, this is not the case with

 

the queries associated

with “Transactions 1” and “Transactions 2” personalized

 

commands for the “TeSys U n°1” node of the gateway’s default configuration. These

 

queries are transmitted when at least one of the values of their output data

 

(addresses 16#0212 to 16#0217 or addresses 16#0218 to 16#0220D) is changed by

 

the Profibus-DP master. So all data from a single query must be updated by the

 

Profibus-DP master at the same time. If you are not certain whether your software is

 

able to update all the output data from a query at the same time, we recommend

 

using “Change of State on trigger” mode for these two commands.

 

- Single Shot

This transmission mode only allows a single Modbus

 

exchange for the whole of the time that the gateway is operating. This exchange

 

takes place just after the initialization of the gateway.

 

- Change of state on trigger

With this aperiodic communication mode, the Modbus

 

query is sent every time that the Profibus-DP master changes the value of an 8-bit

 

counter designated by the “Trigger byte address” element. Please see the description

 

of this element for further information about how to use this communication mode.

Update time

This element is only used by the gateway if “Update mode” is set to “Cyclically”. In this

(10ms)

case, it specifies the query’s transmission period on the Modbus network.

E.g.: With the ATS48, we will be using the configuration shown opposite. The most notable points of this configuration are:

On disconnection the data is reset on one of the two networks.

3 re-transmissions with a 100 ms timeout.

Periodic communications with a cycle time set to 300 ms.

75

Page 74
Image 74
Schneider Electric LUFP7 user manual Default communication mode. The query is transmitted