10. Appendix C: Default Configuration

10.2. Content of the Gateway’s DPRAM Memory

The LUFP7 gateway’s DPRAM memory contains all of the data exchanged between the gateway and the 8 TeSys U motor starters, as well as two special registers only exchanged between the gateway and the Profibus-DP master (words used for managing the downstream Modbus network).

The flow of data exchanged between the TeSys U motor starters, the gateway and the Profibus-DP master is shown below, in order to highlight the role of the gateway’s memory in these exchanges:

TeSys U motor starters

c d e

j

Outputs

Modbus

Inputs

LUFP7 Gateway

OUTPUT data memory zone

INPUT data

memory zone

 

 

 

 

Profibus-DP master

 

Outputs

 

(TSX 57353 + TSX PBY 100)

 

 

 

 

 

 

Profibus-DP

 

 

 

 

 

 

 

 

Inputs

 

 

N.B.: The total number of input and output bytes should be less than or equal to 416 bytes. It is therefore not possible to configure both the maximum number of input bytes and the maximum number of output bytes, which are both equal to 244 bytes.

10.2.1. Input Data Memory Area

The gateway has 244 input bytes. Only the first 32 bytes are used. Byte 12#0012 is used for adjusting the following 16-bit data, so that they can be aligned on even addresses, and for obtaining a total size of 32 input bytes. One should therefore configure only one 32-byte input/output module using a Profibus-DP configuration device such as SyCon.

Service

Address

Size

Description

Managing the downstream Modbus network

16#0000

1 word

Gateway status word

 

16#0002

1 word

Value of the motor starter c status register

Periodic communications

16#0004

1 word

Value of the motor starter d status register

16#0006

1 word

Value of the motor starter e status register

16#0008

1 word

Value of the motor starter f status register

Monitoring of

16#000A

1 word

Value of the motor starter g status register

TeSys U motor starters

16#000C

1 word

Value of the motor starter h status register

 

16#000E

1 word

Value of the motor starter i status register

 

16#0010

1 word

Value of the motor starter j status register

——

16#0012

1 byte

Free memory location

Aperiodic communications

16#0013

1 byte

Slave no. (16#01 to 16#08)

16#0014

1 byte

Function number (16#03)

Reading the value of a

16#0015

1 byte

Number of bytes read (16#02)

motor starter parameter

16#0016

1 word

Value of the parameter read (16#xxxx)

(RESPONSE)

Aperiodic communications

16#0018

1 byte

Slave no. (16#01 to 16#08)

16#0019

1 byte

Function number (16#06)

Writing the value of a

 

 

 

16#001A

1 word

Address of the parameter written (16#xxxx)

motor starter parameter

16#001C

1 word

Value of the parameter written (16#xxxx)

(RESPONSE)

Aperiodic communications

16#001E

1 byte

Read parameter response counter

(“Trigger bytes” for the responses)

16#001F

1 byte

Write parameter response counter

——

16#0020

1 byte

Free input area

(212 bytes)

 

16#00F3

1 byte

 

16#00F4

1 byte

Unusable input area

——

(268 bytes)

 

16#01FF

1 byte

96

Page 95
Image 95
Schneider Electric LUFP7 Content of the Gateway’s Dpram Memory, Input Data Memory Area, Service Address Size Description