8. Appendix B: LUFP7 Gateway GSD File

; Supported baudrates

9.6_supp

= 1

19.2_supp

= 1

45.45_supp

= 1

93.75_supp

= 1

187.5_supp

= 1

500_supp

= 1

1.5M_supp

= 1

3M_supp

= 1

6M_supp

= 1

12M_supp

= 1

Communication rates supported by the LUFP7 gateway.

All rates should be mentioned in this section. The gateway supports all the baud rates of the Profibus-DP networks.

; Maximum responder

time for supported baudrates

Maximum response time of the gateway,

MaxTsdr_9.6

 

= 60

 

 

 

depending on the baud rate of the

MaxTsdr_19.2

 

= 60

 

MaxTsdr_45.45

 

= 60

 

Profibus-DP network.

 

MaxTsdr_93.75

 

= 60

 

 

 

 

MaxTsdr_187.5

 

= 60

 

The response times specified for the

MaxTsdr_500

 

= 100

 

MaxTsdr_1.5M

 

= 150

 

gateway are standard values, compatible

MaxTsdr_3M

 

= 250

 

with

the TSX PBY 100

coupler, for

MaxTsdr_6M

 

= 450

 

example.

 

MaxTsdr_12M

 

= 800

 

 

 

 

; Supported hardware features

 

 

 

 

Redundancy

 

= 0

; not supported

General hardware characteristics specific

Repeater_Ctrl_Sig

= 2

; TTL

to Profibus-DP.

 

24V_Pins

 

= 0

; not connected

 

Implementation_Type

= "SPC3"

 

 

 

 

; Supported DP features

 

 

 

 

Freeze_Mode_supp

= 1

; supported

Supported and not supported Profibus-DP

Sync_Mode_supp

 

= 1

; supported

services.

 

Auto_Baud_supp

 

= 1

; supported

 

Set_Slave_Add_supp

= 0

; not supported

 

 

 

; Maximum polling frequency

 

Maximum polling frequency / Minimum

Min_Slave_Intervall

= 1

; 100 us

polling interval

 

 

 

 

 

100 µs is the smallest interval that can be

 

 

 

 

configured.

 

; Maximum supported

sizes

; modular

The

LUFP7 gateway is

a modular

Modular_Station

= 1

Profibus-DP device, i.e. the size of its I/O

Max_Module

 

= 24

 

Max_Input_Len

 

= 244

 

exchanges on the Profibus-DP network is

Max_Output_Len

 

= 244

 

configured by combining several modules

Max_Data_Len

 

= 416

 

together (see below).

 

Modul_Offset

 

= 1

 

 

 

 

 

 

 

Fail_Safe

 

= 0

; state CLEAR not accepted

Supported and not supported Profibus-DP

Slave_Family

 

= 0

 

services (cont'd).

 

 

 

The length of the gateway's diagnostic data

Max_Diag_Data_Len

= 6

 

should remain equal to 6. N.B. there are no

 

 

 

 

 

 

 

 

parameter data (the “User_Prm_Data_Len

 

 

 

 

and

User_Prm_Data” parameters are

 

 

 

 

therefore omitted).

 

Bitmap_Device

= "LUFP7_R"

 

Names of the bitmap files used by SyCon

Bitmap_Diag

= "LUFP7_D"

 

to display the gateway's connection

Bitmap_SF

= "LUFP7_S"

 

status.

 

; Definition of modules

 

Beginning of the section where the

 

 

 

 

modules used for configuring the sizes of

 

 

 

 

the gateway inputs and outputs are

 

 

 

 

defined.

 

92

Page 91
Image 91
Schneider Electric LUFP7 user manual Maximum response time of the gateway