Schneider Electric PM5100 manual Mechanical Characteristics, Environmental Characteristics

Models: PM5100

1 96
Download 96 pages 2.42 Kb
Page 15
Image 15

PowerLogic™ PM5100 series user guide

Chapter 3—Hardware Reference

 

 

 

 

Power Factor

Class 0.5 as per IEC 61557-12 1

 

Voltage Harmonics

Class 5 as per IEC 61557-12 1

 

Voltage THD/thd

Class 5 as per IEC 61557-12 1

 

Current Harmonics

Class 5 as per IEC 61557-12 1

 

Current THD/thd

Class 5 as per IEC 61557-12 1

 

MID Directive (2004/22/EC)

Annex B and Annex D (PM5111) Class C

 

Input-voltage (up to 1.0 MV AC max, with voltage transformer)

 

 

UL: 20-347 V L-N/35-600 V L-L

 

Nominal Measured Voltage range

IEC: 20-400 V L-N/35-690 V L-L

 

 

(absolute range 35 V L-L to 760 V L-L)

 

Impedance

5 M

 

F nom

50/60 Hz

 

Input-current (configurable for 1 or 5 A secondary CTs)

 

 

I nom

5 A

 

Measured Amps with over range and Crest Factor

Starting current: 5mA

 

Operating range: 50mA to 8.5A

 

 

 

Withstand

Continuous 20 A,10s/hr 50 A, 1s/hr 500 A

 

Impedance

< 0.3 m

 

F nom

50/60 Hz

 

Burden

<0.026VA at 8.5A

 

Frequency measurement

 

 

Measurement range

45 to 65 Hz

 

AC control power

 

 

Operating range

100 - 277 V AC L-N / 415 V L-L +/-10%

 

CAT III 300V class per IEC 61010

 

 

 

Burden

<5 W,11 VA at 415 V L-L

 

Frequency

45 to 65 Hz

 

 

80 mS typical at 120V AC and maximum burden.

 

Ride-through time

100 mS typical at 230 V AC and maximum burden

 

 

100 mS typical at 415 V AC and maximum burden

 

DC control power

 

 

Operating range

125-250 V DC ±20%

 

Burden

<4 W at 250 V DC

 

Ride-through time

50 mS typical at 125 V DC and maximum burden

 

Outputs

 

 

Digital output

 

 

Max load voltage

40 V DC

 

Max load current

20 mA

 

On Resistance

50 max

 

 

from 1 to 9,999,999 pulses per k_h (k_h = kWh,

 

Meter constant

kVARh or kVAh depending on the energy parameter

 

 

selected)

 

Pulse width for Digital Output

50% duty cycle

 

Pulse frequency for Digital Output

25 Hz max.

 

Leakage current

0.03 micro Amps

 

Isolation

5 kV rms

 

Optical outputs

 

 

Pulse width (LED)

200 μs

 

Pulse frequency

50 Hz. max.

 

Meter constant

from 1 to 9,999,999 pulses per k_h

 

Mechanical Characteristics

 

 

 

 

 

Product weight

380 g

 

IP degree of protection (IEC 60529)

IP52 front display, IP30 meter body

 

Dimensions W x H x D [protrusion from cabinet]

96 x 96 x 72mm (depth of meter from housing

 

mounting flange) [13mm]

 

 

 

Mounting position

Vertical

 

Panel thickness

6 mm maximum

 

Environmental Characteristics

 

 

 

 

 

Operating temperature

 

 

Meter

-25 °C to +70 °C

 

Display (Display functions to -25º with reduced

-25 °C to +70 °C

 

performance)

 

 

 

Storage temp.

-40 °C to +85 °C

 

Humidity range

5 to 95% RH at 50 °C (non-condensing)

© 2014 Schneider Electric All Rights Reserved

15

Page 15
Image 15
Schneider Electric PM5100 manual Mechanical Characteristics, Environmental Characteristics