Chapter 5—Viewing Meter Data

PowerLogic™ PM5100 series user guide

 

 

Related topics

See “Current demand” on page 65.

Volts [U-V]

VL-L [U] V L-N [V]

Line-to-line voltage for each phase.

Line-to-neutral voltage for each phase.

Harm

V L-L [U]

Line-to-line voltage harmonics data: Numeric magnitude and

 

 

angle for the fundamental harmonic, and graphical

 

 

 

Fund, 3-11, 7-15

representation of harmonics for the 3rd to 11th and 7th to 15th

 

 

odd harmonics for each line-to-line phase voltage.

V L-N [V]

Line-to-neutral voltage harmonics data: Numeric magnitude and

 

 

angle for the fundamental harmonic, and graphical

 

 

 

Fund, 3-11, 7-15

representation of harmonics for the 3rd to 11th and 7th to 15th

 

 

odd harmonics for each line-to-neutral phase voltage.

Amps [I]

Current harmonics data: Numeric magnitude and angle for the

 

 

fundamental harmonics, and graphical representation of

 

 

 

Fund, 3-11, 7-15

harmonics for the 3rd to 11th and 7th to 15th odd harmonics for

 

 

each phase current.

TDD

Total demand distortion for each phase voltage.

 

 

 

Related topics

See “Power quality” on page 67.

Power [PQS]

 

 

 

 

Summary of real-time power consumption values for total active

Power [PQS]

power [Ptot] in kW, total reactive power [Qtot] in kVAR, and total

 

 

 

 

apparent power [Stot] in kVA.

Phase

Per phase (A [P1], B [P2], C [P3]) and total (Total [Ptot]) power

 

 

 

 

values for active power in kW, reactive power in kVAR and

 

Active [P], Reac [Q], Appr [S]

 

apparent power in kVA.

 

 

 

 

 

 

 

 

 

Summary of peak power demand values in the previous (Last)

Dmd

demand interval period for active power in kW, reactive power in

 

 

 

 

kVAR and apparent power in kVA.

 

 

 

 

Total and per phase (A [1], B [2], C [3]) peak power demand

 

Wd [Pd], VARd [Qd], VAd [Sd]

values in the previous (Last) demand interval for active power

 

demand (Wd [P]), reactive power demand (VARd [Q]) and

 

 

 

 

 

 

 

 

apparent power demand (VAd [S]).

 

 

 

 

 

 

 

 

 

Each of these sub-screens (total and per phase demand) display

 

 

 

 

power demand values for the current (Pres) demand interval,

 

 

Tot, A [P1], B [P2], C [P3]

predicted (Pred) demand based on the current power

 

 

consumption rate, demand for the previous (Last) demand

 

 

 

 

 

 

 

 

interval period, and the recorded peak (Peak) power demand

 

 

 

 

value.

 

 

 

Pk DT

Date and timestamp for the peak (Peak) power demand value.

 

 

 

 

 

Related topics

See “Demand” on page 63.

Energy [E]

Wh

VAh

VARh

Delivered (Del), received (Rec), delivered minus received (D+R) and delivered minus received (D-R) accumulated values for real energy (Wh), apparent energy (VAh) and reactive energy (VARh).

PF

True

Disp

Per phase and total true power factor values and sign.

Per phase and total displacement power factor values and sign.

Hz [F]

Frequency (Freq), average voltage and current (Vavg, Iavg) and power factor (PF) values.