PowerLogic™ PM5100 series user guide

Chapter 6—Input / Output

 

 

3.Navigate to I/O configuration > Energy Pulsing.

4.Select the LED or a digital output to configure and click Edit. The setup screen is displayed.

5.Enter a descriptive name for the digital output’s Label.

6.Configure the other setup parameters as required.

7.Click Send to save your changes.

Alarm / energy pulsing LED setup parameters available through ION Setup

Parameter

Values

Description

 

 

 

 

 

Off disables the LED.

Mode

Off, Alarm, Energy

Alarm sets the LED for alarm notification.

 

 

Energy sets the LED for energy pulsing.

 

 

When configured for energy pulsing, this

Pulse Wt. (p/k_h)

1 to 9999999

defines how many pulses are sent to the LED

for every 1 kWh, 1 kVARh or 1kVAh of

 

 

 

 

accumulated energy.

 

 

 

 

Active Energy Delivered

 

 

 

 

 

Active Energy Received

 

 

 

 

 

Active Energy Del+Rec

 

 

 

 

 

Reactive Energy Delivered

Select which accumulated energy channel to

 

 

Channel

Reactive Energy Received

monitor and use for energy pulsing.

 

 

 

Reactive Energy Del+Rec

 

 

 

 

 

Apparent Energy Delivered

 

 

 

 

 

Apparent Energy Received

 

 

 

 

 

Apparent Energy Del+Rec

 

 

 

 

Related topics

See “Alarm Priorities” on page 53 for a detailed description on the alarm / energy pulsing LED’s behavior when it is configured for alarm notification.

Configuring the alarm / energy pulsing LED using the front panel

You can use the front panel display to configure your meter’s LED for alarming or energy pulsing application.

Alarm / energy pulsing LED settings menu tree

Maint

Reset

Setup

Meter

Comm

Alarm

I/O

HMI

Clock

LED

D out

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to I/O > LED.

4.Move the cursor to point to the parameter you want to modify, then press Edit.

Alarm / energy pulsing LED parameters available through the front panel

Parameter

Values

Description

 

 

 

 

 

Disabled turns off the LED completely.

Mode

Off, Alarm, Energy

Alarm sets the LED for alarm notification.

 

 

Energy sets the LED for energy pulsing.

 

 

When configured for energy pulsing, this setting defines

Pulse Wt. (p/k_h)

1 to 9999999

how many pulses are sent to the LED for every 1 kWh,

 

 

1 kVARh or 1kVAh accumulated energy.

© 2014 Schneider Electric All Rights Reserved

49

Page 49
Image 49
Schneider Electric PM5100 manual Navigate to I/O configuration Energy Pulsing, Parameter Values Description