Schneider Electric PM5100 manual Single resets, Single reset options, Alarm counter options

Models: PM5100

1 96
Download 96 pages 2.42 Kb
Page 78
Image 78

Chapter 11—Meter resets

PowerLogic™ PM5100 series user guide

 

 

Single resets

Single resets allow you to clear data only in a specific register or register type.

1.Navigate to Maint > Reset.

2.Move the cursor to point to Single Reset, then press Select.

3.Move the cursor to point to the parameter you want to reset, then press Reset. If there are additional options for the parameter, press Select, move the cursor to point to the option you want, then press Reset.

Single reset options

Parameter

 

Option

Description

 

 

 

 

Energy

Accumulated

 

Clears all accumulated energy values (kWh,

 

kVARh, kVAh).

 

 

 

 

 

 

Select which demand registers to clear

Demand

Power, Current

(power demand, current demand or input

 

 

 

metering demand).

 

Event Queue

 

Clears the alarm event queue register.

 

 

 

 

 

History Log

 

Clears the alarm history log.

 

 

 

 

Alarms

 

All Alarm Counts,

Select “Counters”, then select which counter

 

Counters

(various alarm

to clear (choose all or individual alarm

 

counters) — see the

counters listed in the “Alarm counter options”

 

 

 

 

next table

table below).

 

 

 

 

Active Load Timer

 

 

Clears and restarts the load operation timer.

 

 

 

 

4.Enter the reset password if prompted (default is “0000”), then press OK.

5.Press Yes to confirm the reset or No to cancel and return to the previous screen.

Alarm counter options

Alarm counter

Option

Description

 

 

 

 

Over Current, Ph

 

 

 

 

Current

Under Current, Ph

Select which alarm counter register to reset from

Over Current, N

the current alarm condition counters.

 

 

 

 

 

Over Current, Gnd

 

 

 

 

 

Over Voltage, L-L

 

 

 

 

 

Under Voltage, L-L

 

 

 

 

 

Over Voltage, L-N

Select which alarm counter register to reset from

 

 

Voltage

Under Voltage, L-N

the voltage alarm condition counters.

 

 

 

Over Voltage Unbal

 

 

 

 

 

Over Voltage THD

 

 

 

 

 

Phase Loss

 

 

 

 

 

Over kW

Select which alarm counter register to reset from

 

 

Power

Over kVAR

the power alarm condition counters.

 

 

 

Over kVA

 

 

 

 

 

Lead PF, True

 

 

 

 

Power Factor

Lag PF, True

Select which alarm counter register to reset from

Lead PF, Disp

the power factor alarm condition counters.

 

 

 

 

 

Lag PF, Disp

 

 

 

 

 

Over kW Dmd, Pres

 

 

 

 

 

Over kW Dmd, Last

 

 

 

 

 

Over kW Dmd, Pred

 

 

 

 

 

Over kVAR Dmd, Pres

Select which alarm counter register to reset from

 

 

Demand

Over kVAR Dmd, Last

the demand alarm condition counters.

 

 

 

Over kVAR Dmd, Pred

 

 

 

 

 

Over kVA Dmd, Pres

 

 

 

 

 

Over kVA Dmd, Last

 

 

 

 

 

Over kVA Dmd, Pred

 

 

 

 

78

© 2014 Schneider Electric All Rights Reserved

Page 78
Image 78
Schneider Electric PM5100 manual Single resets, Single reset options, Alarm counter options, Parameter Option Description