Schneider Electric PM5100 manual Digital outputs, Digital output connections

Models: PM5100

1 96
Download 96 pages 2.42 Kb
Page 27
Image 27

PowerLogic™ PM5100 series user guide

Chapter 3—Hardware Reference

Related topics

To configure RS-485 communications, see “Setting up serial communications” on page 34.

Digital outputs

The meter is equipped with a digital output port (D1). You can configure the digital output for use in the following application:

energy pulsing applications, where a receiving device determines energy usage by counting the k_h pulses (k_h = kWh, kVARh or kVAh depending on the energy parameter selected) coming from the meter’s digital output port.

The digital output can handle voltages less than 40 V DC. For higher voltage applications, use an external relay in the switching circuit.

Digital output connections

D1-/C

(60)(57)

<20mA

LOAD

< 40Vdc

Related topics

See “Digital output applications” on page 47 for digital output use and configuration

details.

© 2014 Schneider Electric All Rights Reserved

27

Page 27
Image 27
Schneider Electric PM5100 manual Digital outputs, Digital output connections