PowerLogic™ PM5100 series user guide

Chapter 3—Hardware Reference

Symbol

Description

 

500 mA fused disconnect / circuit breaker (not supplied)

 

 

 

Shorting block (not supplied)

PT primary fuses and disconnect switch (not supplied)

*Indicates wiring for a balanced system

NOTE:

Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator.

The fuses / circuit breakers must be rated for the installation voltage and sized for the available fault current.

Fuse for neutral terminal is required if the source neutral connection is not grounded.

Potential Transformer

Current Transformer

IEC

ANSI

Power system

This section outlines typical requirements for wiring the voltage and current inputs of the meter to the electrical power system.

For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.

Direct connect voltage limits

You can connect the meter’s voltage inputs directly to the phase voltage lines of the power system if the power system’s line-to-line or line-to-neutral voltages do not exceed the meter’s direct connect maximum voltage limits. The meter's voltage measurement inputs are rated by the manufacturer for up to 400 V L-N / 690 V L-L. However, the maximum voltage allowed for direct connection may be lower, depending on the local electrical codes and regulations. In US and Canada the maximum voltage on the meter voltage measurement inputs may not exceed 347 V L-N / 600 V L-L.

If your system voltage is greater than the specified direct connect maximum voltage, you must use VTs (voltage transformers) to step down the voltages.

22

© 2014 Schneider Electric All Rights Reserved

Page 22
Image 22
Schneider Electric PM5100 manual Power system, Direct connect voltage limits, Symbol Description, Current Transformer