PowerLogic™ PM5100 series user guide

Chapter 3—Hardware Reference

Pollution degree Altitude

For indoor use only

2

2000 m CAT III / 3000 m CAT II

Electromagnetic Compatibility 3

Electrostatic discharge

IEC 61000-4-2

Immunity to radiated fields

IEC 61000-4-3

Immunity to fast transients

IEC 61000-4-4

Immunity to surge

IEC 61000-4-5

Conducted immunity 150kHz to 80MHz

IEC 61000-4-6

Immunity to magnetic fields

IEC 61000-4-8

Immunity to voltage dips

IEC 61000-4-11

Radiated emissions

FCC part 15, EN 55022 Class B

Conducted emissions

FCC part 15, EN 55022 Class B

Safety

 

 

 

Europe

CE, as per IEC 61010-1 (3rd Edition), IEC 62052-11

& IEC61557-12 1

U.S. and Canada

cULus as per UL61010-1 (3rd Edition)

CAN/CSA-C22.2 No. 61010-1 (3rd Edition)

 

Measurement category (Voltage and Current inputs)

CAT III up to 400 V L-N / 690 V L-L

Dielectric

As per IEC/UL 61010-1 (3rd Edition)

Protective Class

II, Double insulated for user accessible parts

Communication

 

 

 

RS-485 port Modbus RTU, Modbus ASCII (7 or 8 bit),

2-Wire, 9600,19200 or 38400 baud, Parity - Even,

Odd, None, 1 stop bit if parity Odd or Even, 2 stop

JBUS

bits if None; (Optional)

 

Firmware and language file update

Meter firmware update via the communication ports

Isolation

2.5 kVrms, double insulated

Human Machine Interface

 

 

 

Display type

Monochrome Graphics LCD

Resolution

128 x 128

Backlight

White LED

Viewable area (W x H)

67 x 62.5 mm

Keypad

4-button

Indicator Heartbeat / Comm activity

Green LED

Energy pulse output / Active alarm indication (configurable)

Optical, amber LED

Wavelength

590 to 635 nm

Maximum pulse rate

2.5 kHz

1For firmware version 1.1.1 and higher

2For 1A nominal CT when I > 0.15A

3Tests are conducted as per IEC 61557-12 (IEC 61326-1), 62052-11 and EN50470

Before you begin

Carefully read and follow the safety precautions before working with the meter.

Safety precautions

Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.

16

© 2014 Schneider Electric All Rights Reserved

Page 16
Image 16
Schneider Electric PM5100 manual Safety precautions, Electromagnetic Compatibility, Communication, Human Machine Interface