6.Depending on the method selected for counting the energy pulses, configure the meter’s alarm / energy LED or one of the digital outputs to perform energy pulsing. Set the meter’s energy pulse constant so it is in sync with the reference test equipment.
7.Perform accuracy verification on the test points. Run each test point for at least 30 seconds to allow the test bench equipment to read an adequate number of pulses. Allow 10 seconds of dwell time between test points.
Calculating the number of required pulses
The reference test equipment typically requires you to specify the number of pulses required for a test duration of “t” seconds.
Use the following formula to calculate the required number of pulses:
| t |
Number of pulses = Ptot × K × |
Where:
•Ptot = total instantaneous power in kilowatts (kW)
•K = the meter’s pulse constant setting, in pulses per kWh
•t = test duration, in seconds (typically greater than 30 seconds)
Calculating total power
The test voltage and current source supplies the same test signals to both the energy reference/standard and the meter under test. Total power is calculated as follows:
For a balanced
1 kW Ptot = 3 × VLN × I × PF ×
1000 W
NOTE: A balanced
For a
1 kW Ptot = VLN × I × PF ×
1000 W
Where:
•Ptot = total instantaneous power in kilowatts (kW)
•VLN = test point
•I = test point current in amps [A]
•PF = power factor
The result of the calculation is rounded up to the nearest integer.
Percent error calculation
For every test point:
EM – ES
Energy Error = --------------------- × 100%
ES