Schneider Electric PM5100 manual Installation and wiring, MID Compliance

Models: PM5100

1 96
Download 96 pages 2.42 Kb
Page 86
Image 86

Chapter 13—MID Compliance

 

PowerLogic™ PM5100 series

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor use only, permanently mounted in residential,

 

Intended use

 

commercial or light industrial applications, where levels of

 

 

 

vibration and shock are of low significance

 

 

Mechanical environment

M1

 

 

 

 

 

Electromagnetic (EMC) environment

E2

 

 

 

 

 

Active Accuracy Class (kWh)

C(kWh)

 

 

 

 

 

 

System types (for MID-compliant applications)

3-phase 4-wire Wye grounded

 

3-phase 3-wire Wye ungrounded

 

 

 

 

 

 

3-phase 4-wire Wye

3 x 63.5(110) to 3 x 277(480) V AC

 

Voltage at voltage

grounded

 

 

 

 

terminals

3-phase 3-wire Wye

3 x 110 to 3 x 480 V L-L

 

 

ungrounded

 

 

 

 

 

Current Rating (Imin – Iref (Imax))

0.05-5(6) A

 

 

 

 

 

Electrical network frequency

50 Hz

 

 

 

 

 

 

 

Location

Meter front panel

 

 

 

 

 

 

Optical pulse output

Frequency

50 Hz maximum

 

 

(energy pulsing LED)

Pulse constant1

10,000 pulses per kWh

 

 

 

Wavelength

590 to 635 nm

 

 

 

 

 

 

Temperature Range

 

-25°C to +70°C

 

 

 

 

 

 

IP Rating

 

IP51

 

 

 

 

 

Insulation Protective Class

Class II

 

 

 

 

 

Impulse Voltage Rating

6kV

 

 

 

 

 

 

AC Voltage Rating

 

4kV

 

 

 

 

 

Main Cover Sealing Type

Wire and Crimp

 

 

 

 

 

Intended Location of the Meter

Indoor

1See “MID-protected setup parameters” on page 88 for additional details.

Safety precautions

Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.

Turn off all power supplying this device before working on it.

Always use a properly rated voltage sensing device to confirm that all power is off.

Do not exceed the device’s ratings for maximum limits.

Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.

Never short the secondary of a voltage transformer (VT).

Never open circuit a current transformer (CT).

Always use grounded external CTs for current inputs.

Failure to follow these instructions will result in death or serious injury.

1.Turn off all power supplying this device before working on it.

2.Always use a properly rated voltage sensing device to confirm that all power is off.

Installation and wiring

Refer to the installation sheet that shipped with your meter for meter installation and wiring instructions.

86