PowerLogic™ PM5100 series user guide

Chapter 3—Hardware Reference

Energy Values*

Accumulated Active, Reactive and Apparent Energy

Received/Delivered; Net and absolute

Demand Values*

Current average

Present, Last, Predicted, Peak, and Peak

Date Time

 

Active power

Present, Last, Predicted, Peak, and Peak

Date Time

 

Reactive power

Present, Last, Predicted, Peak, and Peak

Date Time

 

Apparent power

Present, Last, Predicted, Peak, and Peak

Date Time

 

Demand calculation (Sliding, fixed and rolling block, thermal

methods)

 

Synchronization of the measurement window to input,

communication command or internal clock

 

Settable Demand intervals

 

 

Other Measurements*

Operating timer

Load timer

Alarm counters and alarm logs

Power Quality Measurements

THD, thd (Total Harmonic Distortion) I, V L-N, V L-L per phase

I, V L-N, V L-L

TDD (Total Demand Distortion)

 

 

Individual harmonics (odds)

15th

Data Recording

 

 

 

Min/max of instantaneous values, plus phase identification*

 

 

Alarms with 1s timestamp*

 

 

Min/max log

 

 

I/Os

Digital output

Timestamp resolution in seconds

1

(kWh only)

1

NOTE: *Stored in non-volatile memory

Technical Specifications

Electrical Characteristics

Type of measurement: True rms on three-phase (3P, 3P + N), zero blind

Measurement accuracy

64 samples per cycle

IEC 61557-12 1

PMD/[SDSS]/K70/0.5

Active Energy 2

Class 0.5S as per IEC 62053-22

Reactive Energy 2

Class 2S as per IEC 62053-23

Active Power

Class 0.5 as per IEC 61557-12 1

Reactive Power

Class 2 as per IEC 61557-12 1

Apparent Power

Class 0.5 as per IEC 61557-12 1

Current, Phase

Class 0.5 as per IEC 61557-12 1

Voltage, L-N

Class 0.5 as per IEC 61557-12 1

Frequency

Class 0.05 as per IEC 61557-12 1