PowerLogic™ PM5100 series user guide

Chapter 7—Alarms

Setting Up Unary Alarms

To set up unary alarms:

1.Press Unary. The unary alarm Select screen appears.

2.Press and to scroll through the list of unary alarms.

3.Press Edit to select an alarm to be configured.

4.Press Edit to select Enable.

5.Press + and - to scroll between Yes and No.

6.Press OK to enable or disable the alarm.

7.Press to select Priority.

8.Press + and - to scroll through priority options Low, None, High, or Medium.

NOTE: See “Alarm Priorities” on page 53 for more information.

9.Press OK to set the priority.

10.Press to save all alarms selections and return to the previous screen.

11.Press to save all unary alarm selections.

Viewing Alarm Activity and History

There are two types of alarm entries: primary and secondary. The primary entry identifies the alarm. The secondary entries provide pickup and dropout information.

The active alarm list holds 40 entries at a time. The list works as a circular buffer, replacing old entries as new entries over 40 are entered into the alarm event queue. The information in the alarm event queue reinitializes when the power meter resets.

The alarm history log holds 40 entries. The log also works as a circular buffer, replacing old entries with new entries. This information is nonvolatile.