The function selection is done through configuration register1
Function | Register/device | Remarks |
Phase A | IP 1 (X000) |
|
Phase B | IP 2 (X001) |
|
|
|
|
Reset input | IP 3 (X002) |
|
|
|
|
Comparison value 1 | MW12 MW13 | Data range: 0 to 4294967295 |
Comparison value 2 | MW14 MW15 |
|
|
|
|
Count value | MW16 MW17 |
|
|
|
|
M320 | Operation is enabled when ON | |
Interrupt enable 1 | M322 | Interrupt 1 is enabled when ON |
|
|
|
Count preset 1 | M324 | Used to preset the count value |
|
|
|
Interrupt enable 2 | M323 | Interrupt 2 is enabled when ON |
Count preset 2 | M325 | Used to preset the count value |
|
|
|
Hardware condition:
Phase A and phase B (IP 1 and IP 2)
1X Mode
ON/OFF pulse width: 100 micro sec. or more (max. 5 kHz) 2X Mode
ON/OFF pulse width: 100 micro sec. or more (max. 5 kHz) 4X Mode
ON/OFF pulse width: 100 micro sec. or more (max. 5 kHz)
Reset input (IP3)
ON/OFF duration: 2 ms or more
Interrupt assignment:
Comparison value 1 — I/O interrupt program #1
Comparison value 2 — I/O interrupt program #2
Page 93