No

Device/register

Name

Function

1

MW01_0

CPU error (down)

ON at error state

2

MW01_1

I/O error

ON at error state

3

MW01_2

Program error Clock/calendar

ON at error state

4

MW01_5

error(alarm) Retentive data

ON when clock/calendar data is illegal

5

MW01_6

loss/invalid(alarm) System

ON when retentive data in RAM are invalid

6

MW01_11

Watchdog error (down) I/O

ON at error state

7

MW01_13

mismatch (down)

ON at error state

8

MW01_14

Analog Power Fail I/O

ON at error state

9

MW01_15

BCC error (down)

ON at error state

10

MW02_1

Scan time over (alarm)

ON when the scan time exceeds 200 ms

 

 

 

 

ROM Errors:

If the PLC does not have a program ( Firmware / Application / Ladder ) it remains in the wait loop as given in the Flow Chart. The LEDs are used to indicate these conditions. These errors are not logged in the event history.

No

Condition

Indication

1

No Firmware or Firmware corrupted.

RUN LED and ERR LED blinks at one second interval

 

 

simultaneously.

2

No Application or Application corrupted.

ERR LED blinks at one second interval.

3

No Ladder or Ladder corrupted.

ERR LED blinks at one second interval.

 

 

 

Diagnosis Registers for Serial and Ethernet Communication channels:

Following system registers and system coils can be used for the control and diagnosis of communication channels:

Register / Coil

Tag Name

Read / Write

Description

SW0003_14

COM1 Status

Read only

0 = Communication Error

 

 

 

1= Communicating with Master

SW0003_15

COM2 Status

Read only

0 = Communication Error

 

 

 

1= Communicating with Master

 

 

 

 

SW0003_13

COM3 Status

Read only

0 = Communication Error

 

 

 

1= Communicating with Master

SW0018

COM1 failed node

Read/write

Shows time in sec recover the communication

 

reconnect time (Sec)

 

with failed nodes for port1.the default value is

 

 

 

60Sec

SW0019

COM2 failed node

Read/write

Shows time in sec recover the communication

 

reconnect time (Sec)

 

with failed nodes for port1.the default value is

 

 

 

60Sec

SW0022

COM3 failed node

Read/Write

Shows time in sec recover the communication

 

reconnect time (Sec)

 

with failed nodes for port3.the default value is

 

 

 

60Sec

 

 

 

 

S0021

COM1 failed node

Read/write

If this bit is set communication with the failed

 

reconnect control

 

nodes is detected after scan time SW0018 for

 

 

 

port1.By default : ON

 

 

 

 

Page 125

Page 133
Image 133
Toshiba V200 user manual ROM Errors