No. | Event | Info1 | Info 2 | Info 3 | Info 4 | Special | Meaning and | Check at |
|
|
|
|
|
| Device | countermeasures |
|
|
|
|
|
|
|
|
|
|
6 | Scan | Scan |
|
|
| MW01_2 | The scan time has exceeded 200 | Each main loop |
| time over | time |
|
|
| MW02_1 | mS (Default). (Alarm)Correct the | scan |
|
|
|
|
|
|
| program to reduce the scan time |
|
|
|
|
|
|
|
| or use WDT instruction to extend |
|
|
|
|
|
|
|
| the check time. |
|
|
|
|
|
|
|
|
|
|
7 | System |
|
|
|
|
| Power OFF (no error) | Only |
| power off |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 | System |
|
|
|
|
| Power ON (no error) | Only |
| power on |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9 | WDT Error |
|
|
|
| MW01_00 | The watchdog timer error has | Only |
|
|
|
|
|
| MW01_11 | occurred.(Error down) If the |
|
|
|
|
|
|
|
| error occurs frequently, replace |
|
|
|
|
|
|
|
| the unit. |
|
|
|
|
|
|
|
|
|
|
Page 124