When COM ports are configured as Modbus slaves, the internal PLC tags are mapped to the modbus addresses as given in the following table:

PLC Tag description

Reg. Addressing

Bit Addressing

Modbus address

I/O register

XW(400)

X (6400)

440001 - 440400

 

YW(400)

Y (6400)

441001 - 441400

 

 

 

 

Auxiliary registers

BW00-BW255

B0000 to B4095

442001 - 442256

 

 

 

 

System Registers

SW00-SW256

Not Mapped

420001 - 420256

Timer Registers

T00-T255

Not Mapped

400001 - 400256

 

 

 

 

Counter Register

C00-C255

Not Mapped

410001 - 410256

Data Registers

D0000-D4095

Not Mapped

450001 - 454096

 

 

 

 

Retentive Registers

Not Mapped

430001 - 431400

 

 

 

 

 

Index Register (I,J,K)

I

Not Mapped

443001

 

 

 

 

 

J

Not Mapped

443002

 

K

Not Mapped

443003

Configuration MW registers

MW(1600)

M(25600)

460001-461600

 

 

 

 

COILS:

 

 

 

 

 

 

 

 

 

TR0- TR15

 

Input Coil (R)

 

X (6400)

000001 - 006400

Output Coil (R/W)

 

Y (6400)

010001 - 016400

 

 

 

 

System Coil (R/W)

 

S 0000 to S 0099

020001 - 020100

 

 

 

 

Internal Coil (R/W)

 

B 0000 to B 1023

030001 - 034096

Timer Devices (256 bits = 16 words)

 

T. 000 to T. 255

021001 - 021256

 

 

 

 

Counter Devices (256 bits = 16 words)

 

C. 000 to C. 255

022001 - 022256

Configuration MW coils

 

M(25600)

035001 - 060600

 

 

 

 