When COM ports are configured as Modbus slaves, the internal PLC tags are mapped to the modbus addresses as given in the following table:
PLC Tag description | Reg. Addressing | Bit Addressing | Modbus address |
I/O register | XW(400) | X (6400) | 440001 - 440400 |
| YW(400) | Y (6400) | 441001 - 441400 |
|
|
|
|
Auxiliary registers | B0000 to B4095 | 442001 - 442256 | |
|
|
|
|
System Registers | Not Mapped | 420001 - 420256 | |
Timer Registers | Not Mapped | 400001 - 400256 | |
|
|
|
|
Counter Register | Not Mapped | 410001 - 410256 | |
Data Registers | Not Mapped | 450001 - 454096 | |
|
|
|
|
Retentive Registers | Not Mapped | 430001 - 431400 |
|
|
|
|
|
Index Register (I,J,K) | I | Not Mapped | 443001 |
|
|
|
|
| J | Not Mapped | 443002 |
| K | Not Mapped | 443003 |
Configuration MW registers | MW(1600) | M(25600) | |
|
|
|
|
COILS: |
|
|
|
|
|
|
|
|
| TR0- TR15 |
|
Input Coil (R) |
| X (6400) | 000001 - 006400 |
Output Coil (R/W) |
| Y (6400) | 010001 - 016400 |
|
|
|
|
System Coil (R/W) |
| S 0000 to S 0099 | 020001 - 020100 |
|
|
|
|
Internal Coil (R/W) |
| B 0000 to B 1023 | 030001 - 034096 |
Timer Devices (256 bits = 16 words) |
| T. 000 to T. 255 | 021001 - 021256 |
|
|
|
|
Counter Devices (256 bits = 16 words) |
| C. 000 to C. 255 | 022001 - 022256 |
Configuration MW coils |
| M(25600) | 035001 - 060600 |
|
|
|
|