SW046

Ladder Scan Time

 

Read only

 

Value is multiple of 0.1 mSec

S0034

Ladder Instruction Error

 

Read/Write

 

Set if Division by zero operation is performed in

 

Status

 

 

 

the ladder instruction and for invalid conditions or

 

 

 

 

 

operands in case of conversion instructions.

 

 

 

 

 

 

Configuration Words and coils

 

 

 

 

 

 

 

Register / Coil

Tag Name

Read / Write

Description

 

 

 

 

MW0000

PLC Operation Mode

Read/Write

Bit0-3: 0: Initialization 1: HALT Mode 2: RUN

 

(Bit 0 to Bit 3)

 

 

Mode 3: RUN-F Mode 4: HOLD Mode 6: ERROR

 

 

 

 

 

Mode.

MW0001

Error Register 1

Read Only

Refer mapped coils M16 to M31

MW0002

Error Register 2

Read Only

Refer mapped coils M32 to M47

MW0003

RUN/STOP Switch Control

Read Only

1: HALT, 0: RUN. Only LSB is used. other bits (1

 

(Retentive)

 

 

to 15) are not used.

MW0005

Digital Filter constant

Read/Write

Enabled when MW10 bit 16 is ON.

 

 

 

 

 

(0 to 15 mS)

MW0010

Configuration Register for

Read/Write

Refer Special input - output section

 

Special inputs

 

 

 

MW0011

Configuration Register for

Read/Write

Refer Special input - output section

 

PWM output

 

 

 

MW0012

Preset values for high Speed

Read/Write

Used to set the preset values for high speed

MW0013

Counter

 

 

counter

MW0014

 

 

 

 

 

MW0015

 

 

 

 

 

MW0016

Count Values for high Speed

Read/Write

Preset count values of the high speed counters

MW0017

Counter

 

 

are stored

MW0018

 

 

 

 

 

MW0019

 

 

 

 

 

MW0020

High Speed counter

Read/Write

Control flags for high speed counters

 

control flags

 

 

 

MW0021

Special output control flags

Read/Write

Refer Special input - output section

MW0022

Special Output Control Flags

Read/Write

Control flags for high speed counters

MW0023

 

 

 

 

 

MW0024

Special output Frequency

Read/Write

Refer Special input - output section

 

Setting

 

 

 

MW0025

 

 

 

MW0030

System Timer Coils

Read Only

Refer mapped coils M00480 to M00487

MW0031

User Interrupt program Status

Read Only

Bit 0 for timer ,Bit 1 for IO1, Bit 2 for IO2. Refer

 

Flags

 

 

mapped coils M496,M497 & M498

 

 

 

 

 

when MW10 bit 16 is ON.

MW0033

Unit IP Address Lo Word

Read Only

Used for Ethernet Model

MW0034

Unit IP Address Hi Word

Read Only

 

MW0035

Unit Subnet Mask Address

Read Only

 

 

Lo Word

 

 

 

MW0036

Unit Subnet Mask Address

Read Only

 

 

Hi Word

 

 

 

MW0037

Unit Default Gateway

Read Only

 

 

Lo Word

 

 

 

MW0038

Unit Default Gateway

Read Only

 

 

Hi Word

 

 

 

M00016

CPU error

Read Only

ON at error state

M00017

I/O error

Read Only

ON at error state

M00018

Program error

Read Only

ON at error state. This group includes Ladder

 

 

 

 

 

Scan time.

 

 

 

 

 

 

 

 

Page 80

 

Page 88
Image 88
Toshiba V200 user manual