AC-power wiring

Chapter 6 Installing the EX2 expansion module

Figure 46. Mounting the metal-enclosure EX2

AC-power wiring

Use 16 AWG copper wire for ac-power wiring. All wiring must comply with National Electrical Code and local codes. Use a UL-listed Class 2 power transformer supplying a nominal 24 Vac. The transformer must be sized to provide adequate power to the EX2 module (10 VA) and outputs (a maximum of 6 VA per binary output).

Please read the warnings and cautions before proceeding.

￿WARNING

Hazardous voltage!

Before making line voltage electrical connections, lock open the supply- power disconnect switch. Failure to do so could result in death or seri- ous injury.

￿WARNING

Hazardous voltage!

Make sure that the 24 Vac transformer is properly grounded. Failure to do so could result in death or serious injury.

88

BAS-APG001-EN