Chapter 5 Installing the Tracer MP581 programmable controller
Figure 36. Wiring binary outputs
Powered output
Signal
<1000 ft
(300 m)
| Common |
|
Pilot relay | Tape back shield | |
24 Vac coil | ||
| Signal |
|
|
| < 1000 ft |
| Common | (300 m) |
NOTE: To reduce the potential for transients, locate output devices in the same room with the Tracer MP581.
Checking binary inputs
To check binary inputs for proper operation:
1.Make sure that the sensor is connected and closed.
2.Set the
The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, the input readings may change erratically.
3.Set the
The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, the input readings may be offset.
CAUTION
Equipment damage!
Continue to step 4 only if you completed steps 2 and 3 successfully.
Measuring resistance may damage the meter if the voltage is too high.
4.Set the
The resistance should be less than 200 Ω when the binary input is closed and greater than 1 kΩ when it is open.
70 |