Trane BAS-APG001-EN manual Operational priority, Programming

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 112
Image 112
Chapter 7 Programming

Chapter 7 Programming

In general, the BCU cannot pass information faster than every 5 seconds. This is the fastest a CPL routine can run. A BCU is included to collect system events, such as communication failure, and allow a user a remote connection to the system for status.

Operational priority

(UL 864: 49.10)

The following descending order of priority shall be followed in processing smoke-control commands:

1.Manual activation and deactivation commands issued at the FSCS.

2.Manual activation and deactivation commands at other than the FSCS.

3.Initial automatically actuated smoke-control sequence. The system does not need to override any manual activation or de-activation functions in place prior to the automatic control sequence.

4.All other manual or automatic operation used for normal building operation.

For programming purposes, the priority list in descending order is:

1.Any manual control of dampers, fans, and smoke control panel control.

2.Automatic smoke control system reaction.

3.System test processes such as normal HVAC control, lamp tests, or system self-tests.

All of the above priorities refer to performance, not annunciation. For instance, if a lamp test is running and a user overrides one of the dampers, the annunciation (LED) may not change while the actuator moves. In this case, the lamp test is not affecting system performance, just annunciation. However, if a system self-test is running, either a smoke alarm trigger or manual override will end the self-test. More detail is shown in Table 28 on page 101.

100

BAS-APG001-EN

Page 112
Image 112
Trane BAS-APG001-EN, Engineered Smoke Control System for Tracer Summit manual Operational priority, Programming