Communication watchdog

Communication watchdog

Figure 62. Watchdog communication relationship between a system MP581 and the central FSCP control MP581

Figure 63. Sample TGP showing transmitting during watchdog communication process]

Figure 64. Sample TGP showing watchdog signal receive process

There are three communication signals used in the smoke control system: BCU to MP581, MP581 to MP581, and MP581 to EX-2. The status of all three communication types needs to be indicated at the smoke control panel. Each MP581 collects communication status information from the connected BCU and its associated EX-2 modules and transmits the status back to the smoke control panel MP581. A custom binding, MP580-1/ nvoSwitch39 to MP580-2/nviSwitch37, is used to send the collected status