Chapter 5 Installing the Tracer MP581 programmable controller
Wiring analog outputs
The Tracer MP581 controller has six analog outputs. These outputs can be either
To wire an analog output:
1.For
2.Connect the signal wire to an available analog output terminal
3.Connect the supply wire to a 24 Vac terminal as required.
4.Use the Rover service tool to configure the analog output.
Figure 35. Wiring analog outputs
Ac powered actuator
24 Vac |
|
Signal | < 1000 ft |
| (300 m) |
Common
Signal
Common
<1000 ft
(300 m)
Signal | < 300 ft |
| (100 m) |
Common | Tape back shield |
NOTE: To reduce the potential for transients, locate output devices in the same room with the Tracer MP581.