Trane BAS-APG001-EN manual Pre-installationconsiderations, Equipment, First smoke zone in alarm

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 40
Image 40
First smoke zone in alarm

Chapter 2 Pre-installation considerations

Table 5. Sample automatic smoke control matrix (dedicated)

Equipment

 

First smoke zone in alarm

 

 

 

 

 

 

Zone 1

Zone 2

Zone 3

Zone 4

Main sup fan

On

On

On

On

 

 

 

 

 

Main R/E fan

On

On

On

On

 

 

 

 

 

Stair press fan

On

On

On

On

 

 

 

 

 

1st flr sup dmpr

Close

Open

Close

Close

 

 

 

 

 

1st flr ret dmpr

Open

Close

Close

Close

 

 

 

 

 

2nd flr sup dmpr

Open

Close

Open

Close

 

 

 

 

 

2nd flr ret dmpr

Close

Open

Close

Close

 

 

 

 

 

3rd flr sup dmpr

Close

Open

Close

Open

 

 

 

 

 

3rd flr ret dmpr

Close

Close

Open

Close

 

 

 

 

 

4th flr sup dmpr

Close

Close

Open

Close

 

 

 

 

 

4th flr ret dmpr

Close

Close

Close

Open

 

 

 

 

 

Smoke zone 1

Alarm

Adjacent

Unaffected

Unaffected

 

 

 

 

 

Smoke zone 2

Adjacent

Alarm

Adjacent

Unaffected

 

 

 

 

 

Smoke zone 3

Unaffected

Adjacent

Alarm

Adjacent

 

 

 

 

 

Smoke zone 4

Unaffected

Unaffected

Adjacent

Alarm

 

 

 

 

 

Table 6. Sample automatic smoke control matrix (nondedicated)

Equipment

 

First smoke zone in alarm

 

 

 

 

 

 

Zone 1

Zone 2

Zone 3

Zone 4

Main sup fan

On

On

On

On

 

 

 

 

 

Main R/E fan

On

On

On

On

 

 

 

 

 

Stair press fan

On

On

On

On

 

 

 

 

 

1st flr sup dmpr

Open

Open

Open

Open

 

 

 

 

 

1st flr ret dmpr

Open

Open

Open

Open

 

 

 

 

 

2nd flr sup dmpr

Open

Open

Open

Open

 

 

 

 

 

2nd flr ret dmpr

Open

Open

Open

Open

 

 

 

 

 

3rd flr sup dmpr

Open

Open

Open

Open

 

 

 

 

 

3rd flr ret dmpr

Open

Open

Open

Open

 

 

 

 

 

4th flr sup dmpr

Open

Open

Open

Open

 

 

 

 

 

4th flr ret dmpr

Open

Open

Open

Open

 

 

 

 

 

Smoke zone 1

Alarm

Adjacent

Open

Open

 

 

 

 

 

Smoke zone 2

Adjacent

Alarm

Adjacent

Open

 

 

 

 

 

Smoke zone 3

Open

Adjacent

Alarm

Adjacent

 

 

 

 

 

Smoke zone 4

Open

Open

Adjacent

Alarm

 

 

 

 

 

28

BAS-APG001-EN

Page 40